24 | VWG-50-Setup Guide

BACnet Settings. BACnet MS-TP Settings

MS-TP Address. Is the BACnet MAC address assigned to the VWG. It is a

unique identification number of a device on a BACnet MS-TP network and needs
to be unique on that RS-485 trunk. Usable MS-TP MAC range is from 0 to 127.
Default is value is –1, which disables BACnet MS-TP communication.

MS-TP Baud Rate. Is the assigned Baud rate of the VWG on the BACnet MS-TP

networks. All node on the trunk need to be set to the same speed for proper
operation

Valid and usable ranges are: 9600 Kbps, 19200 Kbps, 38400 Kbps, and 76800
Make sure to click “Enable” after entering the proper settings.