beautypg.com

Viconics VWG-50 (Classic ZigBee) Design Consideration and Setup Guide User Manual

Page 23

background image

23 | VWG-50-Setup Guide

BACnet IP Settings

BACnet Adapter. This selects which of the 2 IP network connections is to be

used for BACnet IP communication. Net1 or Net2. The default is set to Net 1.

UDP Port. Is the default BACnet UDP port number assigned to the device if the

VWG for BACnet IP communication. The default port for BACnet communication
port used is: 47808 (0xBAC0). Do not change this value

Bbmd Address. The BACnet IP Address of the BBMD this foreign device should

register with.

 
Note: A BACnet IP Address requires the HTTP port number of the remote
device (i.e. 192.168.100.120:47808 where 192.168.100.120 is the TCP/IP
address and 47808 is the HTTP port used when redistributing broadcast
messages).

Registration Lifetime. Is the duration of registration with the selected BBMD.

The device will re-register itself periodically before this time expires. Default
value is 15 minutes.


Make sure to click “Enable” after entering the proper settings.