24 | PIR Ready VT7300-2572 Series










Med AO2

Default value: 6.0 V

The middle speed AO2 fan output value when the fan is

enabled.

This value is used only if the fan mode is set to Med.

4.1 to 7.0 V

High AO2

Default value: 8.6 V

The maximum AO2 fan output value when the fan is enabled.

This value is used if the fan mode is set to High and as a

maximum output if the fan output is set to auto.

7.1 to 10.0 V

UI3 dis

Display UI3 value.

Used as diagnostic / service help to troubleshoot and diagnose

sensor operation

Supply or change over temperature when UI3 is configured as

an analog input

( SS or COS )