18 | PIR Ready VT7300-2572 Series

UI3
Universal input no.3
configuration

Default value = None

(None): No function will be associated with the input


(COC/NH) Change over dry contact. Normally Heat: Used
for hot / cold water or air change over switching in 2 pipe
systems.

Contact closed = Cold water or air present

Contact opened = Hot water or air present

Only used and valid if system is setup as 2 pipes. Parameter
(Pipe No) set as 2 pipes.


(COC/NC) Change over dry contact. Normally Cool: Used
for hot / cold water or air change over switching in 2 pipe
systems.
Contact closed = Hot water present
Contact opened = Cold water present
Only used and valid if system is setup as 2 pipes. Parameter
(Pipe No) set as 2 pipes.

(COS) Change over analog sensor: Used for hot / cold
water or air change over switching in 2 pipe systems.

Only used and valid if system is setup as 2 pipes. Parameter
(Pipe No) set as 2 pipes.

If water temperature is > 78 °F = Hot water present

If water temperature is < 75 °F = Cold water present

(SS) Supply air sensor monitoring: Used for supply air
temperature monitoring.

Only used for network reporting of the supply air
temperature. Has no internal function in the Terminal
Equipment Controller.

MenuScro
Menu scroll
Default value = On =
Scroll active

Removes the scrolling display and displays the room
temperature/humidity to the user. With this option enabled,
no mode, schedule and outdoor temperature status is
given.

On = Scroll active

Off = Scroll not active

AutoMode
Enables Auto menu for Mode
button
Default value = On

Enables Auto function for the mode button
For sequences 2, 4 & 5 only

On = Auto active (Off-Cool-Heat-Auto)

Off = auto not active (Off-Cool-Heat)

C or F
Sets scale of the Terminal
Equipment Controller
Default value = °F

°F for Fahrenheit scale

°C for Celsius scale

On hotel models, this sets the default value when the
Terminal Equipment Controller powers up