Page 14: Sequence of operations

background image

14 | PIR Ready VT7300-2572 Series

Single occupied setpoints adjustment

(Local occupied setpoint adjustment when “Stp Func” = Attch Stp )

Unoccupied and stand-by setpoints adjustments

Setting of the stand-by and unoccupied setpoints is done through the network or through
configuration setup only.

Mode button menu sequence

Modes presented to the user are dependent on the sequence of operation selected.

Default mode is shown in bold when sequence of operation parameter is changed.

The available mode can only be changed through the network since there is no local
mode access

Sequence of operations


AutoMode set to ON = Auto system mode active

SEQUENCE SELECTED

MODE MENU

0 = Cooling Only

Off - Cool

1 = Heating Only

Off - Heat

2 = Cooling With Electric Reheat

Off

Auto – Heat – Cool

3 = Heating With Electric Reheat

Off - Heat

AutoMode set to OFF = Auto system mode NOT active

SEQUENCE SELECTED

MODE MENU

0 = Cooling Only

Off - Cool

1 = Heating Only

Off - Heat

2 = Cooling With Electric Reheat

Off

Heat – Cool

3 = Heating With Electric Reheat

Off - Heat

COOLING

MODE

HEATING

MODE

OFF

MODE

AUTO MODE

Setpoint presented to user is the setpoint from
the last action taken by the Terminal Equipment
Controller or the one currently in use.

Both heating and cooling setpoints are changed
simultaneously while respecting the minimum
configured deadband

If the other setpoint is the one desired, then the
MODE button is used to toggle between the
current displayed one and the other.

Cool XX.X

°F or °C

Heat XX.X

°F or °C

No access
to setpoint

Cool XX.X °F or °C and Heat XX.X °F or °C
Both heating & cooling setpoints change simultaneously
Toggle from ( Heat or Cool ) using the system MODE button