Single occupied setpoints adjustment
(Local occupied setpoint adjustment when “Stp Func” = Attch Stp )
Unoccupied and stand-by setpoints adjustments
Setting of the stand-by and unoccupied setpoints is done through the network or through
configuration setup only.
Mode button menu sequence
Modes presented to the user are dependent on the sequence of operation selected.
Default mode is shown in bold when sequence of operation parameter is changed.
The available mode can only be changed through the network since there is no local
mode access
Sequence of operations
AutoMode set to ON = Auto system mode active
SEQUENCE SELECTED
MODE MENU
0 = Cooling Only
Off - Cool
1 = Heating Only
Off - Heat
2 = Cooling With Electric Reheat
Off
– Auto – Heat – Cool
3 = Heating With Electric Reheat
Off - Heat
AutoMode set to OFF = Auto system mode NOT active
SEQUENCE SELECTED
MODE MENU
0 = Cooling Only
Off - Cool
1 = Heating Only
Off - Heat
2 = Cooling With Electric Reheat
Off
– Heat – Cool
3 = Heating With Electric Reheat
Off - Heat
COOLING
MODE
HEATING
MODE
OFF
MODE
AUTO MODE
Setpoint presented to user is the setpoint from
the last action taken by the Terminal Equipment
Controller or the one currently in use.
Both heating and cooling setpoints are changed
simultaneously while respecting the minimum
configured deadband
If the other setpoint is the one desired, then the
MODE button is used to toggle between the
current displayed one and the other.
Cool XX.X
°F or °C
Heat XX.X
°F or °C
No access
to setpoint
Cool XX.X °F or °C and Heat XX.X °F or °C
Both heating & cooling setpoints change simultaneously
Toggle from ( Heat or Cool ) using the system MODE button