beautypg.com

Viconics VT7300F-2572 Installation Manual User Manual

Page 16

background image

16 | PIR Ready VT7300-2572 Series

CONFIGURATION

PARAMETERS

DEFAULT VALUE

SIGNIFICANCE AND ADJUSTMENTS

PswrdSet
Configuration parameters
menu access password
Default value = 0
Range is: 0 to 1000

This parameter sets a password access to prevent
unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration menu.
Range is: 0 to 1000

Com Addr
Terminal Equipment
Controller networking address
Default value = 254
Range is: 0 to 254

For

BACnet™ MS-TP models, the valid range is

from 1 to 127. Default value of 254 disables
BACnet™ communication for the Terminal
Equipment Controller.

For wireless models, the valid range is 0 to 254
with a maximum of 30 Terminal Equipment
Controller per VWG

BI 1
Binary input no.1 configuration
Default value = None

(None): No function will be associated with the input. Input
can be used for remote network monitoring.

(Rem NSB): remote NSB timer clock input. The scheduling
will now be set as per the binary input. It provides low cost
setback operation via a dry contact

Contact opened = Occupied

Contact closed = Unoccupied

(Motion NO) or (Motion NC): Advanced PIR occupancy
functions using a Normally Open (NO) or Normally Closed
(NC) remote PIR motion sensor. Occupancy mode is now
set as per applied PIR function and configuration.
Application information and examples are available in
document: APP-PIR-Guide-Exx. This document will
provide the installers and system designers with detailed
examples on applications, parameter configuration
information, sequence of operation, troubleshooting and
diagnostic help required for the proper usage of the PIR
accessory covers

(Window) EMS: Forces the system to disable any current
heating or cooling action by the Terminal Equipment
Controller. The mode stays the same and the current
setpoints are the same Occupied setpoints. Only the
outputs are disabled. There is a Door/Window alarm
displayed on the Terminal Equipment Controller to indicate
to the local tenant that the door/window needs to be closed
for cooling or heating to resume.

Contact opened = Window Opened

Contact closed = Window Closed

*These settings will disable the local override function on the
Terminal Equipment Controller