23 | PIR Ready VT7300-2572 Series

aux cont
Auxiliary contact function
& configuration
Default value = 0 Not
Used

0 Aux contact function used for reheat
IF SEQUENCE IS SET TO REHEAT THROUGH NETWORK
OR LOCAL
, Ignore this parameter.

The output will directly follow the occupancy of the
Terminal Equipment Controller
1
Auxiliary NO, Occ or St-By = Contact Closed / Unoccupied =
Contact Opened
2 Auxiliary NC, Occ or St-By = Contact Opened / Unoccupied
= Contact Closed

Output to follow directly main occupancy and Fan on
command
Typically used for 2 position fresh air damper applications.
3 Auxiliary NO, Occ or St-By & Fan On = Contact Closed /
Unoccupied & Fan On or Off = Contact Opened
4 Auxiliary NC, Occ or St-By & Fan On = Contact Opened /
Unoccupied & Fan On or Off = Contact Closed

Output to follow secondary network occupancy command
5 Auxiliary On/Off Control through auxiliary network
command. The output can be commanded through the network
for any required auxiliary functions through a separate &
dedicated network variable.

Auto Fan
Auto Fan Function
Default value: AS

Auto Speed Fan Mode operation for Fan Sequences 2 and 3
AS = Auto Speed during occupied periods. Fan is always on
during occupied periods.

AS AD = Auto Speed / Auto Demand during occupied
periods.

RA/DA

For Analog models

VT73xxF5x00(x) only

Default value: DA signal

Reverse acting or Direct acting signal for Analog output signals

DA = Direct acting, 0 to 100 % = 0 to 10 VDC

RA = Reverse acting, 0 to 100 % = 10 to 0 VDC

Reheat

Default value: 0 = 15

minute

Sets the reheat output time base

Valid only if reheat sequences are enabled

0 = 15 minutes

1 = 10 seconds for Solid state relays

Low AO2

Default value: 2.2 V

The minimum AO2 fan output value when the fan is enabled.

This value is used if the fan mode is set to Low and as a

minimum output if the fan output is set to auto.

2.0 to 4.0 V