Viconics VT7300 Installation Manual (Current Release 5000 Series PIR Ready) User Manual
Page 29

29 | PIR Ready VT7300 Series-Installation Guide
Set Type
Temporary setpoint
enable
Default is : Permnent
Enables temporary
setpoints feature to any
change of occupied or
unoccupied setpoint.
Temporar: (temporary) Local changes to the heating or
cooling setpoints by the user are temporary. They will remain
eff
ective for the duration specified by “ToccTime”. Setpoints
will then revert back to their default value after internal timer
“ToccTime” expires.
To change setpoints permanently, revert this variable to No
or write setpoints through the network. Any setpoints written
through the network will be permanent and saved to
EEPROM.
Permnent: (permanent) Any change of occupied or
unoccupied setpoints through the keypad by the user are
permanent and saved to & EEPROM
SptFunc
Local setpoint settings
Default value = Dual
Stp
Set the local setpoint interface for the user
Dual Stp ( Dual Occupied Setpoints Adjustment )
AttchStp ( Single Occupied Setpoint Adjustment )
TOccTime
Temporary occupancy
time
Default value = 2 hours
Temporary occupancy time with occupied mode setpoints
when override function is enabled.
When the Terminal Equipment Controller is in unoccupied
mode, function is enabled with either the menu or UI2
configured as remote override input.
Range is: 0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, & up to 24 hours
Deadband
Minimum deadband
Default value = 2.0 °F
( 1.0 °C )
The minimum deadband value between the heating and
cooling setpoints. When modified, it will take effect only when
any of the setpoints are modified again.
Range is: 2, 3, 4 or 5 °F, 1.0 °F increments ( 1.0 to 2.5 °C,
0.5 °C increments )
Cal RS
Room temperature
sensor calibration
Default value =
0.0 °F or °C
Offset that can be added/subtracted to the actual displayed
room temperature
Range is: ± 5.0 °F, 1.0 °F increments ( ± 2.5 °C, 0.5 °C
increments )
Cal RH
Humidity sensor
calibration
Default value = 0 %RH
Offset that can be added/subtracted to the actual displayed
humidity by ± 15.0 %RH.
Range is : ± 15.0 %RH