beautypg.com

Configuration interface – Viconics VT7300 Installation Manual (Current Release 5000 Series PIR Ready) User Manual

Page 19

background image

19 | PIR Ready VT7300 Series-Installation Guide

Configuration interface

CONFIGURATION

PARAMETERS

DEFAULT VALUE

SIGNIFICANCE AND ADJUSTMENTS

PswrdSet
Configuration parameters
menu access password
Default value = 0
Range is: 0 to 1000

This parameter sets a password access to prevent
unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration
menu.
Range is: 0 to 1000

Com Addr
Terminal Equipment
Controller networking
address
Default value = 254
Range is: 0 to 254

Conditional parameter to

BACnet™ MS-TP models

VT73xxX5x00B

Conditional parameter to Wireless models
VT73xxX5x00W

For

BACnet™ MS-TP models, the valid range is

from 1 to 127. Default value of 254 disables
BACnet™ communication for the Terminal
Equipment Controller.

For wireless models, the valid range is 0 to 254
with a maximum of 30 Terminal Equipment
Controller per VWG

Re-starts the configuration parameter list from the beginning

Enters the configuration mode. Press and hold for 8 seconds


Pressing repetitively will individually scroll all the available parameters

Adjust / rotate parameter value down

Adjust / rotate parameter value up