Configuration interface – Viconics VT7300 Installation Manual (Current Release 5000 Series PIR Ready) User Manual
Page 19

19 | PIR Ready VT7300 Series-Installation Guide
Configuration interface
CONFIGURATION
PARAMETERS
DEFAULT VALUE
SIGNIFICANCE AND ADJUSTMENTS
PswrdSet
Configuration parameters
menu access password
Default value = 0
Range is: 0 to 1000
This parameter sets a password access to prevent
unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration
menu.
Range is: 0 to 1000
Com Addr
Terminal Equipment
Controller networking
address
Default value = 254
Range is: 0 to 254
Conditional parameter to
BACnet™ MS-TP models
VT73xxX5x00B
Conditional parameter to Wireless models
VT73xxX5x00W
For
BACnet™ MS-TP models, the valid range is
from 1 to 127. Default value of 254 disables
BACnet™ communication for the Terminal
Equipment Controller.
For wireless models, the valid range is 0 to 254
with a maximum of 30 Terminal Equipment
Controller per VWG
Re-starts the configuration parameter list from the beginning
Enters the configuration mode. Press and hold for 8 seconds
Pressing repetitively will individually scroll all the available parameters
Adjust / rotate parameter value down
Adjust / rotate parameter value up