25 | PIR Ready VT7300 Series-Installation Guide
%RH disp
Local %RH Display
Default value = Off
Models with Humidity
sensor only
Conditional parameter to Humidity models
VT735xX5x00(X)
Enables the display of humidity value below the room
temperature value on the display
On = Display %RH
Off = No display of %RH
Lockout
Keypad lockout levels
Default value = 0 No lock
USER KEY FUNCTIONS
LEVE
L
0
1
2
3
4
5
Pipe No
System type installation
Number of pipes
Default is: 4.0 Pipes
Defines the type of system installed
2.0 Pipes, will limit the number of sequences of
operation available from 0 to 4
Will enable heat/cool operation from the same output
4.0 Pipes, can access all the sequences of operation
from
0 to 2
Will enable heat/cool operation from different output
CntrlTyp
Control type for Triac
models
Default is: Floating
Defines the type of control output for the type of valves
installed
VT7350C10xx, VT7300C10xx, VT7355C10xx and
VT7305C10xx only
On/Off is for normally opened or normally closed 24 VAC
2 position valves
Floating is for modulating 3 wires control of 24 VAC
floating valves
SeqOpera Sequence of
operation
Default is: Sequence #1
Selects the initial sequence of operation required by the
installation type and the application