25 | PIR Ready VT7300 Series-Installation Guide

%RH disp
Local %RH Display
Default value = Off

Models with Humidity
sensor only

Conditional parameter to Humidity models
VT735xX5x00(X)
Enables the display of humidity value below the room
temperature value on the display

On = Display %RH

Off = No display of %RH

Lockout
Keypad lockout levels
Default value = 0 No lock

USER KEY FUNCTIONS

LEVE

L


0

1

2

3

4

5

Pipe No
System type installation
Number of pipes
Default is: 4.0 Pipes

Defines the type of system installed

2.0 Pipes, will limit the number of sequences of
operation available from 0 to 4

Will enable heat/cool operation from the same output


4.0
Pipes, can access all the sequences of operation
from
0 to 2

Will enable heat/cool operation from different output

CntrlTyp
Control type for Triac
models
Default is: Floating

Defines the type of control output for the type of valves
installed
VT7350C10xx, VT7300C10xx, VT7355C10xx and
VT7305C10xx only
On/Off
is for normally opened or normally closed 24 VAC
2 position valves

Floating is for modulating 3 wires control of 24 VAC
floating valves

SeqOpera Sequence of
operation

Default is: Sequence #1

Selects the initial sequence of operation required by the
installation type and the application