beautypg.com

Viconics VT7300 Installation Manual (Current Release 5000 Series PIR Ready) User Manual

Page 21

background image

21 | PIR Ready VT7300 Series-Installation Guide

Get From
Terminal Equipment
Controller Get From
another device
configuration utility
Default value = 0
Range is: 0 to 254

Conditional parameter to Wireless models
VT73xxX5x00W
Entering a MAC address enables an automatic routine
that automatically fetches all the required configuration
properties of the current device from another already
configured device and copies the same required
configured property values.
If a value other than the default value of 255 is entered,
user will then be prompted to exit the Configuration
Menu thus leaving all other parameter configuration to
be copied from the referenced Terminal Equipment
Controller MAC address.

Ex.: If you are currently configuring MAC12 and the
settings matches exactly the settings of ZN MAC5, then
enter 5 as the current parameter value.

If the process is successful and all required
configuration properties have been copied, the
value will revert back to 255

If the process is NOT successful and all required
configuration properties have NOT been copied
( either the reference device is NOT the same
model number or is offline or does not exists ) the
value will revert back to 254 to indicate the failure
of the process

Leaving the Get From parameter to 255 means that
every configuration parameters will be set
manually.