beautypg.com

Viconics VT7607 BACnet Integration Guide (First Release 1000 Series) User Manual

Page 5

background image

5

Wiring notes:

Note 1: If the same power source is used for the heating stages, install jumper across RC & RH. Maximum current is 2.0

amps.

Note 2: If auxiliary output is used to toggle occupancy of the electronic control card inside the equipment, configure the

relay parameter (Aux cont ) to the N.O. setting. A second relay can be added for additional functionality of the
occupancy output.

Note 3: Humidifier output uses a half bridge rectifier. Reference of the control signal is the common of the power supply of

the thermostat. (terminal C)

Note 4: Electromechanical contact are to be used with the digital input. Electronic triacs cannot be used as mean of

switching for the input. The switched leg to the input for the input to activate is terminal C ( common )

Note 5: The transformer of the unit provides power to the thermostat and the additional loads that will be wired to the

thermostat.

Remote humidity sensor accessories

Model no.

Description

VH2020W1000

Wall mounted humidity sensor

VH2020D10000

Duct mounted humidity sensor






VH2020W1000

, remote wall mounted room humidity sensor.

This sensor can be used for:
• Remote return or room air humidity sensing with the

sensor mounted on the wall.















Fig.7– VH2020W1000
Remote wall mounted sensor


VH2020D1000,

remote duct mounted humidity sensor c/w

junction box.

This sensor can be used for:
• Remote return air humidity sensing with the sensor

mounted on the return air duct.

• Supply air humidity sensor used as a high limit

protection.


Fig.9 – VH2020D1000
Remote duct mounted humidity sensor





Wiring example of remote room humidity sensor:

Wiring example of duct humidity sensor:

HL

OS

Scom

HS

DI

VT76x7 Series
Thermostat

Common

Power

0-10 Vdc

1

2

4

VH2020W1000
Remote wiring

24 Vac Power
To Thermostat

C

RC

HL

OS

Scom

HS

DI

VT76x7 Series
Thermostat

Common

Power

0-10 Vdc

1

2

4

VH2020D1000
Remote wiring

24 Vac Power
To Thermostat

C

RC

Valid for both hight limit sensor (HL) or
main remote humidity sensor (HS) connections


This manual is related to the following products: