Viconics VT7607 BACnet Integration Guide (First Release 1000 Series) User Manual
Page 16
16
Fan del
Fan delay
Default value = Off
Fan delay extends fan operation by 60 seconds
after the call for heating or cooling ends.
Valid only for Auto fan mode. “On” fan mode will
leave the fan always on.
Off or On
Com Addr
Thermostat networking address
Default value = 4
Range is:
0 to 254
• For BACnet MS-TP models valid
range to use is from 1 to 127
• For wireless models valid range is 0
to 254 with a maximum of 30
thermostat per VGG
Conditional parameter to BACnet MS-TP models
(VT76x7B1000B)
Conditional parameter to Wireless models
(VT76x7B1000W)
This parameter will only appear when a BACnet or
wireless network adapter is present. If the
thermostat is installed as a stand-alone unit or with
an Echelon adapter, this parameter will not be used
or displayed
TOccTime
Temporary occupancy time
Default value = 3 hours
Temporary occupancy time with occupied mode
setpoints when override function is enabled
When the thermostat is in unoccupied mode,
function is enabled with either the menu or DI1 or
DI2 configured as remote override input.
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 & 12 hours
Cal RS
Room air temperature sensor calibration
Default value = 0.0 °F or °C
Offset that can be added/subtracted to actual
displayed room temperature
± 5.0 °F ( ± 2.5 °C )
Cal OS
Outside air temperature sensor
calibration
Default value = 0.0 °F or °C
Offset that can be added/subtracted to actual
displayed outside air temperature
± 5.0 °F ( ± 2.5 °C )
H stage
Number of heating stages. Applicable to
2 stage models only
Default value = 2 stages
Will revert the operation of 2 stages thermostat to
single stage operation only when the second
heating step is not needed.
1 or 2 stages
C stage
Number of cooling stages
2 stages model only
Default value = 2 stages
Will revert the operation of 2 stage thermostat to
single stage operation only when the second
cooling step is not needed.
1 or 2 stages
H lock
Outside air temperature heating lockout
Default value = 120 °F ( 49 °C )
Disables heating stage operation based on outdoor
air temperature.
Function will only be enabled if OS ( outside air
temperature sensor ) is connected.
From -15 °F up to 120 °F ( -26 °C up to 49 °C )
C lock
Outside air temperature mechanical
cooling lockout.
Default value = -40 °F ( -40 °C )
Disables cooling stage operation based on outdoor
air temperature.
On economizer model, free cooling will not be
disabled by this function.
Function will only be enabled if OS ( outside air
temperature sensor ) is connected.
From -40 °F up to 95 °F ( -40 °C up to 35 °C )
2/4event
Number of events configuration
Default value = 2 event
For scheduling model only -
VT7657B1000B
2 events
, will set up programming for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
4 events
, will set up programming for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
Event 3 is for Occupied setpoints
Event 4 is for Unoccupied setpoints