beautypg.com

Viconics VT7607 BACnet Integration Guide (First Release 1000 Series) User Manual

Page 19

background image

19

Wireless Model only

PAN ID

Personal Area Network
Identification
Default value = 0
Range is:

0 to 500

Conditional parameter to Wireless models
(VT76x7B1000W)
This parameter will only appear when a wireless
network adapter is present. If the thermostat is
installed as a stand-alone unit or with a BACnet or
Echelon adapter, this parameter will not be used or
displayed

This parameter (Personal Area Network Identification)
is used to link specific thermostats to a single specific
Viconics wireless gateway ( VWG ) For every
thermostat reporting to a gateway ( maximum of 30
thermostats per gateway ), be sure you set the SAME
PAN ID value both at the gateway and the
thermostat(s).

The default value of 0 is NOT a valid PAN ID. The valid
range of available PAN ID is from 1 to 500

Channel

Channel selection
Default value = 10
Range is:

10 to 26

Conditional parameter to Wireless models
(VT76x7B1000W)
This parameter will only appear when a wireless
network adapter is present. If the thermostat is
installed as a stand-alone unit or with a BACnet or
Echelon adapter, this parameter will not be used or
displayed

This parameter (Channel) is used to link specific
thermostats to specific Viconics wireless gateway(s) (
VWG ) For every thermostat reporting to a gateway (
maximum of 30 thermostats per gateway ), be sure
you set the SAME channel value both at the gateway
and the thermostat(s).

Viconics recommends using only the 2 last
channels ( 25-2575MHz and 26-2580MHz )

The default value of 10 is NOT a valid channel. The
valid range of available channel is from 11 to 26

Get From

Thermostat Get From another
device configuration utility
Default value = 0
Range is:

0 to 254

Conditional parameter to Wireless models
(VT76x7B1000W)

This parameter / function is not currently supported by the
wireless thermostats.

This manual is related to the following products: