Installer configuration parameter menu
Configuration can be done through the network or locally at the thermostat.
• To enter configuration, press and hold the middle button (Menu) for 8 seconds
• Press the same middle button repetitively to scroll between all the available parameters
• Use the up and down key to change the parameter to the desired value.
• To acknowledge and save the new value, press the middle button again.
• The next listed parameter is now displayed

Configuration

parameters

Significance

Default value

Adjustments

%RH disp

Local RH Display
Default value = Off

Enables the display of humidity below the room
temperature on the display

On

= Display %RH

Off

= No display of %RH

DI

Digital input no.1 configuration

Open contact input = function not
energized

Closed contact input = function
energized

Default value =

None

None

, No function will be associated with the input

Rem NSB

, remote NSB timer clock input. Will disable

the internal scheduling of the thermostat. The
scheduling will now be set as per the digital input. The
time is still displayed as information, but the menu part
related to scheduling is disabled and no longer
accessible.

Open contact = occupied setpoints

Closed contacts = unoccupied setpoints

RemOVR

Temporary override remote contact.

Disables all override menu function of the thermostat.
The override function is now controlled by a manual
remote momentarily closed contact. When configured
in this mode, the input operates in a toggle mode. With
this function enabled it is now possible to toggle
between unoccupied & occupied setpoints for the
amount of time set by parameter (TOccTime)
temporary occupancy time. When Override is enabled,
an Override status message will be displayed

Filter,

a back-lit flashing Filter alarm will be displayed

on the thermostat LCD screen when the input is
energized

Service,

a back-lit flashing Service alarm will be

displayed on the thermostat LCD screen when the
input is energized

Lockout

Keypad lockout levels

Default value = 0 No lock

0 = No lock
1 = Low level
2 = High level

Level

Resume/
Override

scheduling

Permanent

Occupied and

Unoccupied

Setpoints

Temporary

setpoints

using arrows

Humidity

Setpoints

System mode

setting

Fan mode

setting

Schedules

setting

Clock setting

Permanent

hold

Resume

sched Y/N

Temperat

set Y/N

Up key (▲)

Down key (▼)

Humidity

set Y/N

Sys mode

set Y/N

Fan mode

set Y/N

Schedule

set Y/N

Clock

set Y/N

Schedule
hold Y/N

0

Yes access

Yes access

Yes access Yes

access Yes

access Yes

access Yes

access Yes

access Yes

access

1

Yes access

No access

Yes access

No Access

No access

No access

No access

Yes access No

access

2

No access

No access

No access

No Access

No access No

access No

access Yes

access No

access

Pwr del

Power-up delay

Default value = 10 seconds

On initial power up of the thermostat (each time 24 Vac
power supply is removed & re-applied) there is a delay
before any operation is authorized (fan, cooling or
heating). This can be used to sequence start up
multiple units / thermostat in one location.

10 to 120 seconds