Auxiliary contact configuration
Default value = N.O. normally open
This contact can be used to energize peripheral
devices such as: lighting equipment, exhaust fans,
economizers, etc.
This contact will operate in parallel with the internal
occupied/unoccupied schedule of the thermostat or
the remote NSB contact if DI is used.
When the system is in OFF mode, the contact will
remain in its unoccupied status independently of the
occupied / unoccupied schedule.
Configured
Contact
occupied
status
Contact unoccupied
status
N.O.
Closed Opened
Aux cont
N.C.
opened Closed
Prog rec
Progressive recovery enabled
Default value = Off
Progressive recovery is automatically
disabled if DI is configured as Remote
NSB
For scheduling model only -
VT7657B1000B
Off
, = no progressive recovery
The programmed occupied schedule time is the
time at which the system will restart.
On
, = progressive recovery active.
The programmed occupied schedule time is the
time at which the desired occupied temperature will
be attained. The thermostat will automatically
optimize the equipment start time.
In any case, the latest a system will restart is 10
minutes prior to the occupied period time.
RH LT
Reset RH lower outside temperature
setpoint
Default value = -20°F (-29°C)
Minimum outside air temperature for RH setpoint
reset.
Only valid if an outdoor air sensor is connected at
the thermostat or a network value is transmitted to
the thermostat. See RH HT & RE Sp.
From –40°F up to 15°F (-40°C to –9.5°C)
RH HT
Reset RH higher outside temperature
setpoint
Default value = 32°F (0°C)
Maximum outdoor air temperature for RH setpoint
reset.
Only valid if an outdoor air sensor is connected at
the thermostat or a network value is transmitted to
the thermostat. See RH LT & RE Sp
From 20°F up to 55°F (-6.5°C to 13°C)
HL Sp
RH High limit setpoint
Default value = 85% RH
High humidity limit in the supply.
Only valid if a 0-10 Vdc sensor is connected at the
thermostat – otherwise this feature is disabled
automatically.
From 50% RH up to 90% RH
Dhu OALK
Dehumidification outside air
temperature lockout
Default value = 32°F (0°C)
Outside air temperature under which the
dehumidification sequence is disabled.
Only valid if an outdoor air sensor is connected at
the thermostat or a network value is transmitted to
the thermostat.
From –40°F up to 122°F (-40°C to 50°C)