Symptom

Possible Cause

Corrective Action

Wrong mode selected

Select cooling mode

Thermostat in Unoccupied
mode

Select Occupied Hold in Schedule hold or Override to
force the thermostat Occupied cooling setpoint

Anticycle delay active

Wait, the anticycling period will end and the
equipment will start

Cooling setpoint is satisfied

Lower the cooling setpoint

Cooling lockout attained

1. Mode is locked out based on outside air

temperature

2. Change configuration parameter C Lock to value -

40 °F ( -40 °C ) to by-pass lockout

Thermostat will not call
for cooling

Wiring error

1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RC & Y1. The

cooling should come ON. If it does not, verify wiring

Wrong mode selected

The thermostat will not
turn on the fan

Wiring error

1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RC & G. The fan

should come ON. If it does not, verify wiring

Digital display shows
missing digits or erratic
segments

Defective display

Replace thermostat

RH sensor is out of range

Verify the remote RH sensor or the internal RH
sensor

System Mode in Cool or Off

Change the system mode parameter to heat

System Mode in Auto but a
cooling demand at the
thermostat

Wait: when a heating demand will occur at the
thermostat, humidification will resume

Thermostat will not call
for humidification

High limit sensor is controlling
the humidifier output by
forcing it to 0%

Wait: when the supply humidity will drop below the
high limit setpoint, humidification will resume.

RH sensor is out of range

Verify the remote RH sensor or the internal RH
sensor

System Mode in Heat or Off

Change the system mode parameter to cool

System Mode in Auto but a
heating demand at the
thermostat

Wait: when a cooling demand will occur at the
thermostat, dehumidification will resume

Thermostat will not call
for dehumidification

Outside air temperature is
below the Dhu OALK
parameter

Change the Dhu OALK parameter to a value that will
enable the dehumidification, if desired.