Fan Coil Unit Controller Series
Application Guide
Viconics Technologies Inc.
|
9245 Langelier Blvd.
|
St.-Leonard
|
Quebec
|
Canada
|
H1P 3K9
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0444-01
www.viconics.com
|
February 2015
Appendix A - pASSiVe inFRA-Red SenSoR SpeCiFiCATionS
+-
ref
+-
ref
+-
ref
BACnet
thermostat
1
BACnet
thermostat
2
BACnet
thermostat
3
Notes:
•
Wiring should be daisy chained
•
Always respect polarity
•
If using 2 conductors and shielded wires, connect
shield of each feed together on back of Controller
•
Only ground shield at one location. Do not connect
shield to reference terminal
No communication wires required
Appendix C - SChemATiC oF ConTRoLLeRS oCCUpAnCy SeqUenCe oF opeRATion
Setpoints
Time
Unoccupied cool
Occupied cool
Stand-by cool
72°F
76°F
80°F
Movement detected
-
Stand-by timer reset
Into Stand-by mode
-
Unoccupied timer reset
Stand-by
time
Unoccupied
time
Into Unoccupied
mode
Next movement
detected
70°F
62°F
Unoccupied heat
Occupied heat
Stand-by heat
72°F
66°F
70°F
Deadband
Deadband
Deadband
22°C
24.5°C
26.5°C
22°C
21°C
21°C
19°C
16.5°C
BACnet
®
Communication Wiring
Wireless Communication
Appendix B - opTionAL neTwoRk SeT-Up