Fan Coil Unit Controller Series
Application Guide
Viconics Technologies Inc.
|
9245 Langelier Blvd.
|
St.-Leonard
|
Quebec
|
Canada
|
H1P 3K9
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0444-01
www.viconics.com
|
February 2015
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8300
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 V
ac)
C (Common)
RH
BO8 - Aux Heat
OU9
- Close Cool V
UO10
- Close Heat V
UO11
- Open Cool V
UO12
- Open Heat V
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Mod. & On / Off Control
ZONE DAMPER ACTUATOR
0-10 v 24 v Com.
COMM ON
24 VAC
24 Vac Transformer
PWM DUCT HEATER
SOLID STATE RELAY
S
L
10 k-2
CO SENSOR
SCOM
Sequence of Operation and Wiring
Occupied Mode
During Occupied periods, occupied heating and cooling setpoints
are used.
Stand-by Mode (only available when PIR motion detector
sensor is used)
When equipped with a PIR (Passive Infrared) accessory sensor
the Controller provides advanced active occupancy logic, which
automatically switches occupancy levels from occupied to stand-by
to unoccupied when no motion is detected in the room:
•
During PIR activated stand-by periods, stand-by heating and
cooling setpoints are used.
•
During PIR activated unoccupied periods, the unoccupied-by
heating and cooling setpoints are used.
Unoccupied Mode
During unoccupied periods, unoccupied heating and cooling
setpoints are used.
Local Override
T
he controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.
On Call for Heat
If supply water temperature is higher than 77°F (25°C), valve
modulates from closed to open according to demand. If water
supply temperature is less than 75°F (23.9°C), valve remains
closed. The duct heater operates as a second step.
On Call for Cool
If supply air temperature is less than 75°F (23.9°C), damper
modulates from closed to open according to demand. If water
supply temperature is greater than 77°F (25°C), damper remains
closed.
Options
•
Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
•
Remote wall mounted sensor or return air temperature
sensor can be used instead of internal temperature sensor of
Controller.
•
3 universal inputs can be used and configured for advanced
functionality as required by the application.