Fan Coil Unit Controller Series

Application Guide

Viconics Technologies Inc.

|

9245 Langelier Blvd.

|

St.-Leonard

|

Quebec

|

Canada

|

H1P 3K9

|

Tel: (514) 321-5660

|

Fax: (514) 321-4150

028-0444-01

www.viconics.com

|

[email protected]

February 2015

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

VT8300

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 V

ac)

C (Common)

RH

BO8 - Aux Heat

OU9

- Close Cool V

UO10

- Close Heat V

UO11

- Open Cool V

UO12

- Open Heat V

BACnet +

BACnet -

BACnet REF

UI 16

UI 17

Common

UI 19

UI 20 - RS

Common

UI22 - SS

Mod. & On / Off Control

ZONE DAMPER ACTUATOR

0-10 v 24 v Com.

COMM ON

24 VAC

24 Vac Transformer

PWM DUCT HEATER

SOLID STATE RELAY

S

L

10 k-2

CO SENSOR

SCOM

Sequence of Operation and Wiring

Occupied Mode
During Occupied periods, occupied heating and cooling setpoints
are used.
Stand-by Mode (only available when PIR motion detector
sensor is used)
When equipped with a PIR (Passive Infrared) accessory sensor
the Controller provides advanced active occupancy logic, which
automatically switches occupancy levels from occupied to stand-by
to unoccupied when no motion is detected in the room:

During PIR activated stand-by periods, stand-by heating and
cooling setpoints are used.

During PIR activated unoccupied periods, the unoccupied-by
heating and cooling setpoints are used.

Unoccupied Mode

During unoccupied periods, unoccupied heating and cooling

setpoints are used.
Local Override

T

he controller reverts back to Occupied mode as specified by a

configuration timer when a local override is requested at Controller.

On Call for Heat

If supply water temperature is higher than 77°F (25°C), valve

modulates from closed to open according to demand. If water

supply temperature is less than 75°F (23.9°C), valve remains

closed. The duct heater operates as a second step.
On Call for Cool

If supply air temperature is less than 75°F (23.9°C), damper

modulates from closed to open according to demand. If water

supply temperature is greater than 77°F (25°C), damper remains

closed.

Options

Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).

Remote wall mounted sensor or return air temperature
sensor can be used instead of internal temperature sensor of
Controller.

3 universal inputs can be used and configured for advanced
functionality as required by the application.