beautypg.com

Vt8300, Fan coil unit controller series application guide, Modulating & pwm control – Viconics VT8300 Low Voltage Application Guide User Manual

Page 51: Fcu low-voltage, Sequence of operation and wiring, Options

background image

©

2

01

5 V

ic

onc

is

T

ec

hno

lo

gi

es

. A

ll r

ig

ht

s r

ese

rv

ed

.

51

Fan Coil Unit Controller Series

Application Guide

Viconics Technologies Inc.

|

9245 Langelier Blvd.

|

St.-Leonard

|

Quebec

|

Canada

|

H1P 3K9

|

Tel: (514) 321-5660

|

Fax: (514) 321-4150

028-0444-01

www.viconics.com

|

[email protected]

February 2015

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

VT8300

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 V

ac)

C (Common)

RH

BO8

- Aux Heat

OU9

- Clos

e Cool V

UO10

- Close Heat V

UO11

- Open Cool V

UO12

- Open Heat V

BACnet +

BACnet -

BACnet REF

UI 16

UI 17

Common

UI 19

UI 20 - RS

Common

UI22 - SS

Modulating & PWM Control

COMM ON

24 VAC

FCU Low-voltage

TERMINAL BLOCK

DUCT HEATER, SRC

0-10 V 24V Com.

PERMETER HEAT

SOLID STATE RELAY

ZONE DAMPER

COOLING ONLY

ACTUATOR

0-10 V 24V Com.

S

L

Sequence of Operation and Wiring

Occupied Mode
During Occupied periods, occupied heating and cooling setpoints
are used.
Stand-by Mode (only available when PIR motion detector
sensor is used)
When equipped with a PIR (Passive Infrared) accessory sensor
the Controller provides advanced active occupancy logic, which
automatically switches occupancy levels from occupied to stand-by
to unoccupied when no motion is detected in the room:

During PIR activated stand-by periods, stand-by heating and
cooling setpoints are used.

During PIR activated unoccupied periods, the unoccupied-by
heating and cooling setpoints are used.

Unoccupied Mode

During unoccupied periods, unoccupied heating and cooling

setpoints are used.
Local Override

The Controller reverts back to Occupied mode as specified by a

configuration timer when a local override is requested at Controller.

On Call for Heat

The damper remains closed. The proportional heater acts as a first

step and modulate from 0 to 100% capacity. The perimeter heater

operates as a second step.
On Call for Cool
The damper modulates from closed to open according to demand.

Options

Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).

Remote wall mounted sensor or return air temperature
sensor can be used instead of internal temperature sensor of
Controller.

3 universal inputs can be used and configured for advanced
functionality as required by the application.