Fan Coil Unit Controller Series

Application Guide

Viconics Technologies Inc.

|

9245 Langelier Blvd.

|

St.-Leonard

|

Quebec

|

Canada

|

H1P 3K9

|

Tel: (514) 321-5660

|

Fax: (514) 321-4150

028-0444-01

www.viconics.com

|

[email protected]

February 2015

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

VT8300

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 V

ac)

C (Common)

RH

BO8

- Aux Heat

UO9

- Close Cool V

UO10

- Close Heat V

UO11

- Open Cool V

UO12

- Open Heat V

BACnet +

BACnet -

BACnet REF

UI 16

UI 17

Common

UI 19

UI 20 - RS

Common

UI22 - SS

Mod. & PWM Control

HEATING VALVE

0-10 v 24 v Com.

COMM ON

24 VAC

24 Vac Transformer

PWM DUCT HEATER

SOLID STATE RELAY

S

L

10 k-2

CO SENSOR

SCOM

Sequence of Operation and Wiring

Occupied Mode
During Occupied periods, the occupied heating and cooling
setpoints are used.
Stand-by Mode (only available when PIR motion detector
sensor is used)
When equipped with a PIR (Passive Infrared) accessory sensor
the Controller provides advanced active occupancy logic, which
automatically switches occupancy levels from Occupied to Stand-by
to Unoccupied when no motion is detected in the room:

During PIR activated stand-by periods, stand-by heating and
cooling setpoints are used.

During PIR activated unoccupied periods, unoccupied-by
heating and cooling setpoints are used.

Unoccupied Mode

During unoccupied periods, unoccupied heating and cooling

setpoints are used.
Occupied Override Mode

The Controller reverts back to Occupied mode as specified by a
configuration timer when a local override is requested at Controller.

On Call for Heat

If supply water temperature is less than 75°F (23.9°C), the valve

modulates from closed to open according to demand. If water

supply temperature is greater than 77°F (25°C), valve remains

closed.
On Call for Cool

If supply water temperature is higher than 77°F (25°C), valve

modulates from closed to open according to demand. If water

supply temperature is less than 75°F (23.9°C), valve remains

closed. The duct heater operates as a second step.

Options

Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).

Remote wall mounted sensor or return air temperature
sensor can be used instead of internal temperature sensor of
Controller.

3 universal inputs can be used and configured for advanced
functionality as required by the application.