Fan Coil Unit Controller Series
Application Guide
Viconics Technologies Inc.
|
9245 Langelier Blvd.
|
St.-Leonard
|
Quebec
|
Canada
|
H1P 3K9
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0444-01
www.viconics.com
|
February 2015
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8300
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 V
ac)
C (Common)
RH
BO8 - Aux Heat
UO11
- Analog Heat
UO12
- Analog Cool
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 193
UI 20 - RS
Common
UI22 - SS
Modulating Control
COOLING VALVE
0-10 V 24V Com.
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
FCU Low-voltage
TERMINAL BLOCK
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Analog valve modulates allowing cool air to flow to reach setpoint.
On Call for Heat
Valve closes.
Options
•
Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
•
Remote wall mount or duct sensor ready.
•
Can be configured for 4-pipe systems.
•
3 universal inputs can be used and configured for advanced
functionality as required by the application.
•
Can be configured to two or three speed fan.