Fan Coil Unit Controller Series

Application Guide

Viconics Technologies Inc.

|

9245 Langelier Blvd.

|

St.-Leonard

|

Quebec

|

Canada

|

H1P 3K9

|

Tel: (514) 321-5660

|

Fax: (514) 321-4150

028-0444-01

www.viconics.com

|

[email protected]

February 2015

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

VT8300

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 V

ac)

C (Common)

RH

BO8 - Aux Heat

UO11

- Analog Heat

UO12

- Analog Cool

BACnet +

BACnet -

BACnet REF

UI 16

UI 17

Common

UI 193

UI 20 - RS

Common

UI22 - SS

Modulating Control

COOLING VALVE

0-10 V 24V Com.

COMM ON

24 VAC

FAN HI

FAN MED

FAN LO

FCU Low-voltage

TERMINAL BLOCK

Sequence of Operation and Wiring

Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Analog valve modulates allowing cool air to flow to reach setpoint.
On Call for Heat
Valve closes.

Options

Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).

Remote wall mount or duct sensor ready.

Can be configured for 4-pipe systems.

3 universal inputs can be used and configured for advanced
functionality as required by the application.

Can be configured to two or three speed fan.