beautypg.com

Vt8300, Sc1300, Fan coil unit controller series application guide – Viconics VT8300 Low Voltage Application Guide User Manual

Page 53: Sequence of operation and wiring, Options

background image

©

2

01

5 V

ic

onc

is

T

ec

hno

lo

gi

es

. A

ll r

ig

ht

s r

ese

rv

ed

.

53

Fan Coil Unit Controller Series

Application Guide

Viconics Technologies Inc.

|

9245 Langelier Blvd.

|

St.-Leonard

|

Quebec

|

Canada

|

H1P 3K9

|

Tel: (514) 321-5660

|

Fax: (514) 321-4150

028-0444-01

www.viconics.com

|

[email protected]

February 2015

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

VT8300

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 V

ac)

C (Common)

RH

BO8 - Aux Heat

UO11

- Analog Heat

UO12

- Analog Cool

BACnet

+

BACnet

-

BACnet REF

UI 16

UI 17

Common

UI 19

UI 20 - RS

Common

UI22 - SS

Mix Voltage 120 volts

SC1300

FAN HI

FAN MED

FAN LO

COMM ON

High Voltage Fan

Power supply

120 Vac

COOLING VALVE

0-10v 24v Com.

HEATING VALVE

0-10v 24v Com.

Sequence of Operation and Wiring

Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve
closes. Dehumidification enabled.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve
closes. Dehumidification disabled.

On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for
reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is
enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low
ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.

Options

Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).

Remote wall mount or duct sensor ready.

Can be configured for 2-pipe systems.

3 universal inputs can be used and configured for advanced
functionality as required by the application.

Universal input can be configured for changeover sensor.