beautypg.com

Vt8300, Fan coil unit controller series application guide, On / off control – Viconics VT8300 Low Voltage Application Guide User Manual

Page 33: Fcu low-voltage terminal block, Sequence of operation and wiring, Options

background image

©

2

01

5 V

ic

onc

is

T

ec

hno

lo

gi

es

. A

ll r

ig

ht

s r

ese

rv

ed

.

33

Fan Coil Unit Controller Series

Application Guide

Viconics Technologies Inc.

|

9245 Langelier Blvd.

|

St.-Leonard

|

Quebec

|

Canada

|

H1P 3K9

|

Tel: (514) 321-5660

|

Fax: (514) 321-4150

028-0444-01

www.viconics.com

|

[email protected]

February 2015

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

1 2 3 4 5 6

13 14 15 16 17 18

7 8 9 10 11 12

19 20 21 22 23 24

VT8300

BO2 - Fan L

BO3 - Fan M

BO4 - Fan H

RC (24 V

ac)

C (Common)

RH

BO8 - Aux Heat

UO9 -

Close Cool V

UO10 -

Close Heat V

UO11 -

Open Cool V

UO12 -

Open Heat V

BACnet +

BACnet -

BACnet REF

UI 16

UI 17

Common

UI 19

UI 20 - RS

Common

UI22 - SS

On / Off Control

COOLING VALVE

IF NC IF NO Com.

COMM ON

24 VAC

FAN HI

FAN MED

FAN LO

FCU Low-voltage

TERMINAL BLOCK

S

L

Sequence of Operation and Wiring

Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
The changeover sensor sends supply air temperature to controller.

Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens. Electric heat stays Off.
On Call for Heat
Valve closes. Electric heat activates.

Options

Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).

Remote wall mount or duct sensor ready.

Can be configured for 4-pipe systems.

3 universal inputs can be used and configured for advanced
functionality as required by the application.

Can be configured to single or two speed fan.