Vt8300, Fan coil unit controller series application guide, On / off control – Viconics VT8300 Low Voltage Application Guide User Manual
Page 33: Fcu low-voltage terminal block, Sequence of operation and wiring, Options
©
2
01
5 V
ic
onc
is
T
ec
hno
lo
gi
es
. A
ll r
ig
ht
s r
ese
rv
ed
.
33
Fan Coil Unit Controller Series
Application Guide
Viconics Technologies Inc.
|
9245 Langelier Blvd.
|
St.-Leonard
|
Quebec
|
Canada
|
H1P 3K9
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0444-01
www.viconics.com
|
February 2015
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
VT8300
BO2 - Fan L
BO3 - Fan M
BO4 - Fan H
RC (24 V
ac)
C (Common)
RH
BO8 - Aux Heat
UO9 -
Close Cool V
UO10 -
Close Heat V
UO11 -
Open Cool V
UO12 -
Open Heat V
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
On / Off Control
COOLING VALVE
IF NC IF NO Com.
COMM ON
24 VAC
FAN HI
FAN MED
FAN LO
FCU Low-voltage
TERMINAL BLOCK
S
L
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector
sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and
cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by
“ToccTime” parameter.
On Call for Cool
Cooling valve opens. Electric heat stays Off.
On Call for Heat
Valve closes. Electric heat activates.
Options
•
Wireless adapter modules for BACnet models are available.
(see Appendix B for network wiring).
•
Remote wall mount or duct sensor ready.
•
Can be configured for 4-pipe systems.
•
3 universal inputs can be used and configured for advanced
functionality as required by the application.
•
Can be configured to single or two speed fan.