Emergency control input settings, P. 51), Emergency control input settings.) – Toa VM-3000 Series User Manual
Page 51

51
(1) VM-3000VA/VM-3000E
Click the box or double-arrow button to select the VM-3000VA or VM-3000E to be set. The display
switches to the setting screen for the selected model. (Note that the setting screen for the VM-3000VA is
the same as that for the VM-3000E.)
(2) Emergency Key Functions (Applicable only to the VM-3000VA)
Set the functions of the VM-3000VA's front panel-mounted keys related to emergency broadcasts.
Each function of Emergency Start, Evacuation EV, and Alert EV can be switched to ON (indicated green)
or OFF (indicated gray) with each click of the radio button.
Note
These functions can be set only when all the versions of VM-3000VA firmware, VM-3000E firmware, and
VM-3000 Setting Software are 2.00 or later.
(3) No.
Represents the number of the emergency control input terminal located on the rear panel of the VM-
3000VA or VM-3000E.
Inputs 1 to 5 are contact inputs while Input 6 is a voltage control input to be activated when the polarity of
24 V DC kept being normally applied is reversed.
(1)
(2)
(3)
(4)
(5)
(6)
10.2. Emergency Control Input Settings
Pressing the "Emergency Setting" button on the Event Setting screen displays the emergency control input
setting screen.
Set whether or not to use the VM-3000VA's Emergency, Evacuation, and Alert keys.
Assign such functions to the emergency control inputs as broadcast activation and End of line function.
When setting the broadcast activation function, also set the sound source, broadcast zones, and interlocked
control outputs.