3 notification appliance circuit terminals, 3 for det – SilentKnight 5499 9A Distributed Power Module User Manual
Page 9

System Overview
151253
5
3.3
Notification Appliance Circuit Terminals
Terminals 3 through 10 are the notification appliance circuit output terminals. Each of
the four circuits are rated at 3 amps, although you can only draw a total of 9 amps
from the 5499. The 5499 outputs are short-circuit protected (power limited) according
to UL 864 standards. Overcurrent indicators are yellow LEDs. The output voltage can
vary depending on the load and input voltage.
The four power-limited NAC outputs can be configured as follows:
•
Four Class B circuits
•
Faraday synchronized outputs
•
Two Class A circuits
•
Gentex synchronized outputs
•
One Class A and two Class B circuits
•
System Sensor synchronized outputs
•
Class B, ANSI temporal-coded circuits
•
Wheelock synchronization outputs
• AMSECO synchronized outputs
One or both 5499 signal inputs control the NAC outputs, depending on the specific
configuration setup. Possible configurations for the 5499 are:
For Option:
These Inputs:
Control These Outputs:
As:
1
Input 1
All outputs
Class B circuits
2
Input 1 or
Outputs 1, 2, 3, and 4
Class B ANSI temporal-
Input 2
coded circuits
3
Input 1
Outputs 1 and 2
Class B circuits
Input 2
Outputs 3 and 4
Class B circuits
4
Input 1
Output 1
Class B circuits
Input 2
Outputs 2, 3, and 4
Class B circuits
5
Input 1
Outputs 1-2 and 3-4
Class A circuit pairs
6
Input 1
Outputs 1 and 2
Class B ANSI temporal-coded
circuits
Input 2
Outputs 3 and 4
Class B circuits
7
Input 1
Outputs 1-2
Class A circuit pair
Input 2
Outputs 3-4
Class A circuit pair
8
Input 1
Outputs 1-2
Class A circuit pair
Input 2
Outputs 3 and 4
Class B circuits
9
Input 1 (Strobe
Control)
All outputs
Class A or Class B
Input 2 (Audio Control)
Faraday Sync. Output
10
Input 1 (Strobe
Control)
All outputs
Class A or Class B
Input 2 (Audio Control)
Gentex Sync. Output
11
Input 1 (Strobe
Control)
All outputs
Class A or Class B
Input 2 (Audio Control)
System Sensor Sync. Output
12
Input 1 (Strobe
Control)
All outputs
Class A or Class B
Input 2 (Audio Control)
Wheelock Sync. Output