5499 Distributed Power Module Installation Manual

10

151253

Table 4-2: Battery Calculation Worksheet

Device

Number of

Devices

Current per Device

Standby

Current

Alarm

Current

For each device use this formula: This column

X This column

= Current per number of

devices.

5499 Distributed Power Module

(Current draw from battery)

1

Standby:

75 mA

75 mA

Alarm:

205 mA

205 mA

A

5499 Current

75 mA

205 mA

Auxiliary Devices

Refer to device manual for current ratings.

Alarm/Standby

mA

mA

mA

Alarm/Standby

mA

mA

mA

Alarm/Standby

mA

mA

mA

Alarm/Standby

mA

mA

mA

B

Auxiliary Device Current

mA

mA

Notification appliances

Refer to device manual for current ratings.

Alarm:

mA

0 mA

mA

Alarm:

mA

0 mA

mA

Alarm:

mA

0 mA

mA

Alarm:

mA

0 mA

mA

C

Notification Appliance Current

0 mA

mA

D

Total current ratings of all devices in system (line A + line B + line C)

mA

mA

E

Total current ratings converted to amperes (line D x .001):

A

A

F

Number of standby hours (24 or 60 for NFPA 72, Chapter 1, 1-5.2.5). 24 Hrs. for
NBC, section 3.2.7.8

H

G

Multiply lines E and F.

Total standby AH

AH

H

Alarm sounding period in hours. In accordance with NBC and ULC.
(For example, 5 minutes = .0833 hours.)

H

I

Multiply lines E and H.

Total alarm AH

AH

J

Add lines G and I.

Total standby and alarm AH

AH

K

Multiply line J by 1.20.
(20% extra insurance to meet desired performance)

Total ampere-hours

required

AH