beautypg.com

3 setting the loss of ac delay, 4 setting the auxiliary output, Section 4.8.4 for det – SilentKnight 5499 9A Distributed Power Module User Manual

Page 26

background image

5499 Distributed Power Module Installation Manual

22

151253

4.8.3

Setting the Loss of AC Delay

Normal selection for reporting loss of AC is 3 hours.

The ON position is for test purposes only and the normal position for Switch 4 is OFF.
For testing the Low AC reporting, you can temporarily turn Switch 4 ON without
removing power.

Note: Remember to turn the switch OFF when testing is complete.

Figure 4-14 Setting DIP Switch 4

4.8.4

Setting the Auxiliary Output

Switch 5 on the DIP switch determines how the auxiliary power operates on the 5499.

The 5499 checks Switch 5 only when powering up the 5499. If you change this
switch, you must remove both the AC power and the battery to force the 5499 to
recognize the new switch setting.

Figure 4-15 Setting DIP Switch 5