beautypg.com

3 service procedures (cont'd) – Reznor CAUA Users Manual User Manual

Page 8

background image

Form O-CAUA, Page 8

FIGURE 5 - Integrated Ignition

Control Module, P/N 195573

Control Status - Green LED

Steady ON

Normal Operation, No call for heat

Fast Flash

Normal Operation, Call for heat

1 Flash

System Lockout, Failed to detect or sustain flame

2 Flashes

Pressure Switch in Open Position

3 Flashes

High Limit or Flame Rollout Switch Open

4 Flashes

Pressure Switch is closed before venter is energized

Steady Off

Internal Failure - Replace the ignition control module

Flame Status - Yellow LED

Steady On

Flame is sensed

Slow Flash Weak Flame

Fast Flash

Undesired Flame

Fan Delay to

OFF Switch (DIP

Switch Settings -

selected prior to

call for heat)

SW1

SW2

Fan Delay To OFF (seconds)

OFF

OFF

120

OFF

ON

90

ON

OFF

160 (Factory Preset)

ON

ON

45

Ignitor Connection

3.0 SERVICE - Control Location, Operation, and Service (cont'd)

1) Call for Heat - The heating/cooling system controller

calls for heat. The ignition system circuit board

checks to see that the limit switch is closed and

the pressure switch is open. If the limit switch is

open, the circuit board responds as defined in the

“Abnormal Heat Cycle, Limit Switch Operation”. If the

pressure switch is closed, the circuit board will do

four flashes on the green LED and wait indefinitely for

the pressure switch to open. If the pressure switch is

open, the circuit board proceeds to prepurge.
2) Prepurge - The circuit board energizes the venter

motor and waits for the pressure switch to close. If

the pressure switch does not close within 30 seconds

of the venter motor energizing, the circuit board will

do two flashes on the green LED. The circuit board

will leave the venter motor energized indefinitely as

long as the call for heat remains and the pressure

switch is open.
When the pressure switch is proven closed, the

circuit board begins the prepurge time. If flame is

present any time while in prepurge, the prepurge time

is restarted. If flame is present long enough to cause

lockout, the circuit board responds as defined in

“Fault Modes, Undesired Flame”.
The ignition system circuit board runs the venter

motor for a 20 second prepurge time, then proceeds

to the ignition trial period.

3) Ignition Trial Period - The ignition system circuit

board energizes the spark and main gas valve. The

venter remains energized. If flame is sensed during

the first 16 seconds, the spark is de-energized.

If flame has not been sensed during the first 16

seconds, the control de-energizes the spark output

and keeps the gas valve energized for an additional

one second flame proving period. If flame is not

present after the flame proving period, the control

de-energizes the gas valve and proceeds with ignition

re-tries as specified in “Abnormal Heat Cycle, Ignition

Retry”. If flame is present, the circuit board proceeds

to steady heat.

4) Steady Heat - Circuit board inputs are continuously

monitored to ensure limit and pressure switches

are closed, flame is established (sensor on both

burner sections), and the system controller call for

heat remains. When the call for heat is removed, the

ignition system circuit board de-energizes the gas

valve and begins postpurge timing.

5) Post Purge - The venter motor output remains on

for a 45 second postpurge period after the system

controller is satisfied.

Normal Heat Cycle Operating Sequence

Service: The direct spark integrated circuit board is polarity sensitive. If burners cycle

on and off, try switching the power supply leads. The supply connection made to "L1"

on the circuit board must be the "hot" wire.
The only replaceable component of the control module is the 3 amp Type ATC or ATO

fuse.
If it is determined that any of the components of the ignition system require replacing,

use only the factory-authorized replacement parts that are designed for this heater.

3.3 Service Procedures (cont'd)

3.3.2 Ignition System (cont'd)

Lights