beautypg.com

Reznor CAUA Users Manual User Manual

Page 15

background image

Form O-CAUA, P/N 164772 R7, Page 15

IMPORTANT: When using a multimeter to troubleshoot the 24 volt circuit, place the meter’s test leads into the 5 or 9

pin connectors located on the ignition control. Do not remove connectors or terminals from the electrical components.

Doing so can result in misinterpreted readings due to the ignition control board’s fault mode monitoring circuits.

Trial for Ignition - Call for Heat

Is there a

spark across gap at

ignitor?

Does gas

ignite?

Is there minimum

flame current at the

flame sensor?

Is there

minimum flame current

at the control

module?

Replace control

module.

Check connections to flame

sensor and/or moisture in the

burner assembly.

Is the flame

sensor corroded?

Clean flame

sensor.

Is the sensor

located in flame

correctly?

Replace flame

sesnsor.

Reposition

flame sensor.

Is gas

flowing?

Is the ignitor

position correct in the

gas flow?

Check gas pressure

and supply voltage.

If either are low,

correct and repeat

startup.

Reposition

spark ignitor.

Is there

24VAC at the gas

valve?

Is there 24VAC

from gas valve output on

control module to

chassis?

Check wiring and

connections to

gas valve.

Replace

ignition

control

module.

Replace gas

valve.

Is there

spark voltage at

control?

Check high

voltage wire

continuity.

Is there 24V P1-2

to power control?

Replace

control

module.

Check wiring

and/or 24VAC

transformer output.

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

NO

YES

YES

NO

YES

NO

YES

NO

DSI Integrated Control Module (Circuit

Board) Trial Troubleshooting Flowchart

General Troubleshooting

PROBLEM PROBABLE CAUSE

REMEDY

Venter

motor will

not start

1. No power to unit.

1. Turn on power, check supply fuses or circuit breaker.

2. No 24 volt power to venter relay.

2. Turn up thermostat; check control transformer output.

3. Integrated ignition control module defective.

3. Replace integrated ignition control module. DO NOT ATTEMPT TO REPAIR CONTROL MODULE; IT

HAS NO FIELD REPLACEABLE COMPONENTS.

4. Defective venter motor.

4. Replace venter motor.

Burners will

not light

1. Manual valve not open.

1. Open manual valve.

2. Air in the gas line.

2. Bleed gas line.

3. Door switch open.

3. Close blower compartment door. If door is closed, replace switch.

4. Gas pressure is too high or too low.

4. Set supply pressure at 5" to 14" w.c. for natural gas and 11" to 14" w.c. for propane.

5. No Spark:

5.

a) Loose wire connections

a) Be certain all wire connections are solid.

b) Transformer failure

b) Be sure 24 volts is available.

c) Incorrect spark gap.

c) Maintain spark gap at 1/8".

d) Spark cable shorted to ground.

d) Replace worn or grounded spark cable.

e) Spark electrode shorted to ground

e) Replace if ceramic spark electrode is cracked or grounded.

f) Burners not grounded

f) Make certain ignition control module is grounded to the ignitor.

g) Ignition control module not grounded.

g) Make certain ignition control module is grounded to the furnace chassis.

h) Faulty integrated ignition control module

h) If 24-volt is available to the integrated ignition control module and all other causes have been eliminated,

replace module. DO NOT ATTEMPT TO REPAIR IGNITION CONTROL MODULE; IT HAS NO FIELD

REPLACEABLE COMPONENTS.

6. Lockout device interrupting control circuit by

above causes.

6. Reset lockout by interrupting control at the thermostat or main power.

7. Faulty combustion air proving switch.

7. Replace combustion air proving switch.

8. Main valve not operating.

8.

a) Defective valve

a) If 24 volt is measured at the valve connections and valve remains closed, replace valve.

b) Loose wire connections

b) Check and tighten all wiring connections.

9. Ignition module does not power the valve.

9.

a) Loose wire connections

a) Check and tighten all wiring connections.

b) Flame sensor grounded

b) Be certain flame sensor lead is not grounded or insulation/ceramic is not cracked. Replace as required.

c) Incorrect gas pressure

c) Set supply pressure at 5" to 14" w.c. for natural gas and 11" to 14" w.c. for propane.

d) Cracked ceramic at sensor

d) Replace sensor.

10. Flame rollout switch open

10.

a) Air blockage through the unit

a) Check for heat exchanger or vent pipe blockage.

b) Faulty flame rollout switch

b) Replace flame roll out switch.

Burners

cycle on

and off

1. Gas pressure is too high or too low.

1. Set supply pressure at 5" to 14" w.c. for natural gas and 11" to 14" w.c. for propane.

2. Burners not grounded

2. Make certain ignition control module is grounded to the ignitor.

3. Ignition control module not grounded.

3. Make certain ignition control module is grounded to the furnace chassis.