beautypg.com

3 service procedures (cont'd) – Reznor CAUA Users Manual User Manual

Page 12

background image

Form O-CAUA, Page 12

3.0 SERVICE - Control Location, Operation, and Service (cont'd)

3.3 Service Procedures (cont'd)

3.3.7 Transformer

Function: The 40VA transformer reduces the supply voltage to a 24-volt circuit in order

to operate the 24-volt controls.
Transformer Check (requires a volt meter): To verify the 24-volt circuit, check the

operation of the transformer. Set the thermostat to above room temperature. Using a

voltmeter, check the voltage between Terminal R on the thermostat terminal strip and

the ground terminal on the ignition controller. If there is no voltage in this circuit, the

transformer is not functioning. The service of a transformer is like that of a light bulb; it

is either good or bad and when bad, it must be replaced.
Service: If replacement of the transformer is necessary, do not substitute any other

transformer. Use replacement transformer IDENTICAL to the factory-installed models.
IMPORTANT NOTE: Do not short the "hot" side of the transformer to ground when

servicing the heater. Doing so will cause the transformer to fail.

40VA

Transformer

in the Heater

Electrical Box,

P/N 164328

40VA

Transformer

in the Optional

Mixing Box,

P/N 103497

3.3.8 Blower Motor and

Drive

Location/Function: The blower motor and blower are located in the blower compart-

ment at the bottom of the heater.

NOTE: The blower compartment door is equipped

with a safety switch. If the door is not closed, the heater will not operate.
The function of the motor and drive is to provide airflow through the heat exchanger

and supply air to the space. Model CAUA units are equipped either with a direct-drive

or a belt-drive blower and motor.
Size 150 and 200 heaters equipped with direct-drive have one 1HP blower motor. A

Size 150 has a 12-9 blower and a Size 200 has a 12-12 blower. Sizes 250-400 have

dual 1HP blower motors and dual 12-9 blowers.
Sizes 150-200 with belt-drive have a single motor and blower; sizes 250-400 have a

single motor and dual blowers. Motor ranges in size from 1/4 to 5 HP.
For information on how to adjust the blower speed, see Form I-CAUA, Paragraph 6.5.

CAUTION: An external duct system static pressure not within the limits

shown on the rating plate, or improper motor pulley or belt adjustment,

may overload the motor. See Hazard Levels, Page 2.

For information on replacing a belt, see Maintenance Section, Paragraph 2.2.1.

Function: The blower compartment door is equipped with a safety

switch. If the door is not closed securely, the heater will not operate.

Service: If it is determined that the blower compartment door switch

needs replacing, use only the factory-authorized replacement part

that is designed for use on this heater.

Door Switch, P/N 116023

Inlet Air Dampers

Location: Dampers and controls are located in the optional outside air/return air mix-

ing box. (Potentiometer may be remotely located.)

Function: Dampers operate in response to controls. See controls below and applica-

tion by option in

TABLE 5, page 14.

Service: Clean dampers and controls of dust or dirt.

2-Position Damper Motor

Function: The 2-position damper motor opens and closes the dampers. Damper posi-

tion is either on when the unit is operating or is determined by a two-position enthalpy

control.

Service: There is no service required on this motor other than external cleaning. If

the motor needs replaced, replace with an identical damper motor or damper motor

replacement kit.

Modulating Damper Motor

Function: The modulating damper motor actuates the dampers in response to a

potentiometer or a mixed air controller. Outside air dampers close when the heater

shuts down.

Service: There is no service required on this motor other than external cleaning. If the

motor needs replaced, replace with an identical damper motor.

3.3.9 Blower

Compartment Door

Switch

3.3.10 Inlet Air Dampers

and Controls

2-Position

Damper

Motor

Modulating

Damper

Motor