Charging the Unit in AC mode at outdoor temperatures

above 55° F for optimized sub-cooling of 10° F - 12° F.

1. With the system operating at steady-state, measure the

liquid refrigerant pressure (in psig) at the outdoor unit
service valve.

2. Measure the liquid refrigerant temperature (in

Fahrenheit) at the service valve.

3. Determine the required liquid refrigerant pressure from

the appropriate charging chart (Figures 3 - 9).

• If the pressure measured in Step 1 is greater than

the required liquid refrigerant pressure determined in
Step 3, then there is too much charge in the system.
Remove refrigerant and repeat Steps 1 through 3
until the system is correctly charged.

• If the pressure measured in Step 1 is less than the

required liquid refrigerant pressure determined in
Step 3, there is too little charge in the system. Add
refrigerant and repeat Steps 1 through 3 until the
system is correctly charged.

application notes for using charging charts

• This equipment’s cooling system contains

refrigerant under high pressure. always use
safe and environmentally sound methods when
handling refrigerant handling or servicing the unit.
review the factory literature and safety warnings
prior to servicing.

• When repairing system leaks, always use a nitrogen

(inert) gas to protect the refrigerant system and pressure
check the repair before re-charging. Always replace
the filter-dryers when performing any repair to the

refrigeration system with one capable of acid removal.
After completing the repairs, evacuate the system to
350 - 500 microns and weigh in the refrigerant to the
amount specified on the unit rating label.

• Charging charts are valid for a variety of indoor, return

air conditions and are most influenced by the outdoor
ambient temperature, outdoor fan operation and the
unit operating voltage. Before using these charts, make
sure the unit is in a stable operating mode. As shown
in the charging charts (Figures 3 - 9, pages 8 - 11), the
ideal system sub-cooling can vary over the range of
operation. Reference the charts to determine the ideal
amount of sub-cooling for a given liquid pressure. Units
charged to other values will not perform at the rated unit
efficiency (EER) or rated Coefficient of Performance
(COP) in heating mode.

• To inspect a systems operation using quality

instruments, match the measured liquid temperature
to the units chart. The measured liquid pressure
reading should be within 3% of the charts value for
most installations.

• For systems that are operating with more than a 5%

deviation, inspect the unit for the proper voltage and
phase balance and the refrigeration system for leaks.

• Units that are operating at less then 95% of the nominal

voltage or with a 2% phase imbalance may see a more
significant deviation than the amount stated above.

do not use the charts in systems that have a
fan cycling under low-ambient control. Refer to the
low-ambient kit instructions for more information. (If
applicable)

250

275

300

325

350

375

400

425

450

475

500

525

550

575

600

70

75

80

85

90

95

100

105

110

115

120

125

130

Liquid Temperature (F)

Liquid Pressure (psig)

Remove refrigerant when above the curve

Add refrigerant when below the curve

figure 3. charging chart for S4Bd-018 Series (1.5 ton units) - tXV matches

S4Bd refrigerant charging chartS