S4bd refrigerant charging tables - cooling only – Reznor JS4BD (1ph) Unit Installation Manual User Manual
Page 12

12
table 3. charging table for S4Bd-018 Series (1.5 ton units) - orifice matches
Suct.
press.
outdoor temperature (°f)
70
75
80
85
90
95
100
105
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
132
257
137
134
258
140
280
140
136
259
144
281
144
304
144
138
260
147
282
147
305
147
327
147
140
261
150
283
150
306
150
328
150
351
150
142
284
153
307
153
329
153
352
153
374
154
144
308
156
330
156
353
157
375
157
398
157
146
331
159
354
159
376
160
399
160
421
160
148
333
162
355
162
377
163
400
163
422
163
150
356
165
379
166
401
166
423
166
152
380
169
402
169
424
169
154
403
172
426
172
156
427
175
158
table 4. charging table for S4Bd-024 Series (2 ton units) - orifice matches
Suct.
press.
outdoor temperature (°f)
70
75
80
85
90
95
100
105
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
125
256
136
127
257
139
280
139
129
258
143
281
143
304
143
131
259
146
282
146
305
146
328
146
133
260
150
283
150
306
150
329
150
352
150
135
284
153
307
153
330
153
353
153
376
153
137
308
157
331
156
354
157
377
157
400
157
139
333
160
355
160
378
160
401
160
424
160
141
334
163
357
163
379
163
402
164
425
164
143
358
166
381
166
403
167
426
167
145
382
169
405
170
428
170
147
406
173
429
173
149
431
176
151
S4Bd refrigerant charging taBleS - cooling only
legend
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering
dry bulb, or entering wet bulb temperatures are lower than design.
noteS:
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.