Reznor JS4BD (1ph) Unit Installation Manual User Manual

Page 15

background image

15

Suct.

press.

outdoor temperature (°f)

70

75

80

85

90

95

100

105

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

liq.

press.

dis.

temp.

121

264

149

123

265

153

289

153

125

267

156

290

157

313

157

127

268

159

291

160

314

161

338

161

129

270

162

293

163

316

164

339

165

362

165

131

294

166

317

167

340

168

363

169

387

169

133

319

170

342

171

365

172

388

173

411

173

135

343

174

366

175

389

176

412

177

435

178

137

345

177

368

178

391

179

414

180

437

181

139

369

181

392

182

415

183

438

184

141

394

185

417

186

440

187

143

418

189

441

190

145

442

193

147

table 9. charging table for S4Bd-060 Series (5 ton units) - orifice matches

legend

Shaded boxes indicate flooded conditions.

Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering

dry bulb, or entering wet bulb temperatures are lower than design.

noteS:
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.