Reznor JS4BD (1ph) Unit Installation Manual User Manual
Page 13

13
table 5. charging table for S4Bd-030 Series (2.5 ton units) - orifice matches
Suct.
press.
outdoor temperature (°f)
70
75
80
85
90
95
100
105
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
126
278
132
128
280
135
303
137
130
281
138
305
140
328
141
132
283
141
306
143
330
144
354
145
134
284
145
308
146
331
147
355
148
379
149
136
309
149
333
150
357
151
380
152
404
154
138
334
153
358
154
382
156
406
157
429
158
140
360
157
384
159
407
160
431
161
454
162
142
361
161
385
162
409
163
432
164
456
165
144
387
164
411
166
434
167
457
168
146
412
168
436
170
460
171
148
438
172
462
173
150
464
176
152
table 6. charging table for S4Bd-036 Series (3 ton units) - orifice matches
Suct.
press.
outdoor temperature (°f)
70
75
80
85
90
95
100
105
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
124
261
137
126
263
141
287
140
128
265
144
288
143
312
142
130
266
147
290
146
313
146
337
145
132
268
150
292
149
315
149
339
148
362
147
134
293
153
317
152
340
152
364
151
387
150
136
318
155
342
154
365
154
389
153
413
152
138
344
158
367
157
390
157
414
156
438
155
140
345
161
369
160
392
160
416
159
439
158
142
370
163
394
163
417
162
441
162
144
396
166
419
165
442
165
146
421
168
444
168
148
446
171
150
legend
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering
dry bulb, or entering wet bulb temperatures are lower than design.
noteS:
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.