Reznor JS4BD (1ph) Unit Installation Manual User Manual
Page 14

14
table 7. charging table for S4Bd-042 Series (3.5 ton units) - orifice matches
Suct.
press.
outdoor temperature (°f)
70
75
80
85
90
95
100
105
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
130
257
135
132
259
138
282
138
134
261
141
283
142
306
142
136
262
144
285
145
307
145
330
146
138
264
146
286
147
309
149
331
149
354
150
140
288
150
310
151
333
152
355
153
378
153
142
312
154
334
155
357
156
379
156
402
157
144
336
158
358
159
381
160
404
160
426
161
146
337
161
359
162
382
163
405
163
428
164
148
361
165
383
166
406
166
429
167
150
385
169
407
169
430
170
152
408
172
431
173
154
432
176
156
table 8. charging table for S4Bd-048 Series (4 ton units) - orifice matches
Suct.
press.
outdoor temperature (°f)
70
75
80
85
90
95
100
105
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
liq.
press.
dis.
temp.
125
261
136
127
262
140
285
140
129
263
143
286
143
309
144
131
265
146
287
147
310
147
333
148
133
266
149
289
149
311
151
334
151
357
151
135
290
152
312
153
335
154
358
155
381
155
137
314
156
336
157
359
158
382
159
405
159
139
338
160
360
161
383
162
406
163
429
163
141
339
163
361
164
384
165
407
166
430
166
143
363
167
385
168
408
169
431
170
145
387
171
409
172
432
173
147
410
175
433
176
149
434
179
151
legend
Shaded boxes indicate flooded conditions.
Rated design values. The suction pressure will be lower than design value if outdoor air flow, entering
dry bulb, or entering wet bulb temperatures are lower than design.
noteS:
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures GREATER than charted values indicate an UNDERCHARGED system.
3. Discharge temperatures LESS than charted values indicate an OVERCHARGED system.