beautypg.com

Warning – Reznor JS4BD (1ph) Unit Installation Manual User Manual

Page 7

background image

7

refrigerant charging

Warning:

S4Bd Split System air conditioners are shipped
charged with r410a refrigerant and ready
for installation. if repairs make it necessary
for evacuation and charging, it should only
be attempted by qualified trained personnel
thoroughly familiar with this equipment. under
no circumstances should the owner attempt to
install and/or service this equipment. failure to
comply with this warning could result in property
damage, personal injury, or death.

After refrigerant line connections are completed, it is
required that you leak check and evacuate the indoor
section and all line connections (using proper methods)

before finalizing the full system refrigerant charge.
• Refrigerant charging charts are applicable only to

matched assemblies of NORDYNE equipment and
listed airflows for the indoor coil. Refer to Figures 3 -
9 (pages 8 - 11) and Tables 3 - 9 (pages 12 -15) for
correct system charging.

• S4BD outdoor units with non-AHRI listed indoor coils

are not recommended. Deviations from rated airflows or
non-listed combinations may require modification to the
expansion device and refrigerant charging procedures
for proper and efficient system operation.

• The refrigerant charge can be checked and adjusted

through the service ports provided external to the
outdoor unit. Use only gage line sets which have a
“Schrader” depression device present to actuate the
valve.

• A high-pressure switch is factory-installed and located

in the liquid line internal to the outdoor unit. The switch
is designed to protect the system when very high
pressures occur during abnormal conditions. Under
normal conditions, the switch is closed. If the liquid
pressure rises above 575 psig, then the switch will

open and de-energize the outdoor unit. The switch

will close again once the liquid pressure decreases
to 460 psig. Please note that the switch interrupts the
thermostat inputs to the unit. Thus, when the switch
opens and then closes, there may be a 5 minute short

cycling delay before the outdoor unit will energize.

• A low-pressure switch (Select Models) is factory-

installed and located in the suction line internal to
the outdoor unit. The switch is designed to protect
the compressor from a loss of charge. Under normal
conditions, the switch is closed. If the suction pressure
falls below 5 psig, then the switch will open and de-

energize the outdoor unit. The switch will close again

once the suction pressure increases above 20 psig.
Please note that the switch interrupts the thermostat
inputs to the unit. When the switch opens and then
closes, there will be a 5 minute short cycling delay

before the outdoor unit will energize.

Start up & adjuStmentS

pre-Start check list

Verify the indoor unit is level and allows proper

condensate drainage.

Verify the outdoor coil and top of the unit are free from

obstructions and debris, and all equipment access/
control panels are in place.

Verify air filters are cleaned and properly installed.

Verify duct work is sealed to prevent air leakage.

Verify line voltage power leads are securely connected

and the unit is properly grounded.

Verify low voltage wires are securely connected to the

correct leads on the low voltage terminal strip.

Verify power supply branch circuit overcurrent

protection is sized properly.

Verify the thermostat is wired correctly.

Start-up procedures
The thermostat's function mode should be set to OFF and
the fan mode should be set to AUTO. Close all electrical

disconnects to energize the system.

Air Circulation - Indoor Blower
1. Set the thermostat system mode on OFF and the fan

mode to ON.

2. Verify the blower runs continuously. Check the air delivery

at the supply registers and adjust register openings for
balanced air distribution. If insufficient air is detected,
examine ductwork for leaks or obstructions.

3. Set the thermostat fan mode to AUTO and verify the

blower stops running.

System Cooling
1. Set the thermostat’s system mode to COOL and the

fan mode to AUTO. Gradually lower the thermostat
temperature setpoint below room temperature and

verify the outdoor unit and indoor blower energize.

2. Verify blower wheel is spinning in direction indicated by

arrow. Feel the air being circulated by the indoor blower
and verify that it is cooler than ambient temperature.
Listen for any unusual noises. If unusual sounds occur,
determine the source of the noise and correct as
necessary.

3. Verify HI and LO refrigerant pressures.
4. Allow the system to operate for several minutes and then

set the temperature selector above room temperature.
Verify the fan and compressor cycle off with the
thermostat. note: The blower should also stop unless
fan mode is set to the ON position.

System Heating (optional)
1. Set the thermostat's system mode to HEAT and the

temperature mode above room temperature.

2. Verify the optional heating equipment (furnace or

electric heat) and indoor blower energize. Feel the air

being circulated by the indoor blower and verify that
it is warmer than ambient temperature. Listen for any
unusual noises. If unusual sounds occur, determine the
source of the noise and correct as necessary.