beautypg.com

Installation instructions (cont'd) – Reznor X Option - Option - Installation - Power Venter User Manual

Page 8

background image

Form I-X Venter, P/N 136958R1, Page 8

WARNING

Units installed in multiples require individual vent pipe runs and

vent caps. Manifolding of vent runs is not permitted

5. Install Vent Pipe (cont'd)

Figure 8A - Vertical Vent Terminal

WARNING

Vent terminal arrangements illustrated are applicable only to units with a power venter.

Horizontal vent termination requires a power venter. DO NOT use horizontal vent with

gravity venting.

6’ (2M) minimum

6’ (2M) minimum

Approved clearance thimble

for single-wall vent pipe is

required when flue pipe

extends through

combustible materials.

Parapet or Adjoining Building

Vertical flue extension to

be 6” (152mm) higher than

anticipated snow depth but

no less than 2 feet (610mm)

above the roof.

Vertical pipe extension

must be insulated.

Roof Flashing

Roof - pitched

from 0 to 45°

Vertical flue extension

to be 6” (152mm) higher

than anticipated snow

depth but no less than

2 feet (610mm) above the

roof.

6” (152mm) minimum

Roof Flashing

Roof - pitched

from 0 to 45°

Approved clearance thimble

for single-wall vent pipe is

required when flue pipe extends

through combustible materials.

Follow the requirements of the

double-wall pipe manufacturer.

Follow instructions on page 6

to join single and double-wall

pipe and to seal the connection.

Parapet or Adjoining Building

Single-Wall Vent Run and

Single-Wall Terminal End

Single-Wall Vent Run and

Double-Wall Terminal End

Installation

Instructions

(cont'd)