Danger this reznor – Reznor X Option - Option - Installation - Power Venter User Manual
Page 5

Form I-X Venter, P/N 136958R1, Page 5
4. Electrical Wiring -- Follow the wiring diagram in FIGURE 6A or 6B for wiring the
venter to the heater. Use flexible conduit for both line voltage and control voltage wir-
ing.
All wiring and connections, including electrical grounding, MUST be in accordance with
the National Electric Code ANSI/NFPA No. 70 (latest edition) or in Canada, with the
Canadian Electrical Code, Part I-C.S.A. Standard C22.1. In addition, the installation
must comply with local ordinances and applicable gas company requirements.
DANGER
This Reznor
®
venter must be installed and wired in accordance with these installation
instructions. The venter pressure switch MUST be wired in series with the thermostat to
interrupt the main gas valve circuit. After installation, pressure switch operation MUST be
checked to verify proper operation. See Hazard Levels, page 1.
FIGURE 6A -
Wiring Diagram
for Model X unit
with Power Vent
This wiring
diagram applies
to units with spark
pilot, block vent
switch, and power
venter
sub-assembly with
a pressure swtich.
See NOTES top
of page 6.
FACTORY WIRING
FIELD WIRING
WHITE - W
PURPLE - PR
BLUE - BL
GREEN - G
YELLOW - Y
ORANGE - O
RED - R
BROWN - BR
BLACK - BK
WIRING CODE
TOTAL WIRE MINIMUM RECOMMENDED
LENGTH WIRE SIZE
150 FEET #18 GA.
250 FEET #16 GA.
350 FEET #14 GA.
FIELD CONTROL WIRING
BLOWER MOTOR
CUSTOMER'S
CONTACTOR COIL
CR
DISCONNECT SWITCH
115/1/60
G
GRD
BL
R
Y
LIMIT
CONTROL
W
OPTIONAL SINGLE ST
AGE THERMOST
AT
R
WIRING IN VENTER (SHIPPED SEPARATE)
R
BK
R
BK
2
4
CONTACTS
VENTER RELAY
W
BK
W
BK
Y
8
7
8
10
7
4
11
6
7
7
7
BK
BR
H
TD
H
BR
BR
7
BK
BL
16
FAN TD
HEATER
MAIN
PILOT
BLOCKED VENT
SWITCH
MANUAL RESET
1
Y
CR
11
COIL
VENTER RELAY
BR
BL
BL
BK
PRESSURE
SWITCH
3
1
B
40 VA. CONTROL
BK
BL
24V
115V
BR
TRANSFORMER
Y
VENTER MOTOR
& CAPACITOR
(SEE NOTES)
REDUND
ANT
GAS V
AL
VE
AL
TERNA
TE
W
.R. OR R
OBER
TSHA
W
BL
P
BK
BR
M
AIN
PIL
O
T
M
C
PV
PIL
O
T
MV
PV-MV
M
AIN
REDUND
ANT
GAS V
AL
VE
HONE
YWELL
TERMINAL BLOCK -- HEATER COMPARTMENT
10, 11, B & W
CONTACTS
FAN TD
1
3
THERMAL SWITCH
6
Y
BK
Y
BL
IGNITION
CONTROLLER
PROBE
GND
SPARK
FLAME SENSING
MV/PV
MV
SENSE
TH
PV
24V GND
BR
GND BURNER
G
BURNER
GROUND
BK
- DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED BY OTHERS: BLOWER RELAY
BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105° C., EXCEPT FOR
- CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST
- THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT: THERMOSTAT
- THE FOLLOWING CONTROLS ARE SUPPLIED BY REZNOR FOR FIELD INSTALLATION: VENTER
- LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SHOULD BE SIZED TO
PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.
SENSOR LEAD WIRE WHICH MUST BE 150° C.
NOTES
- USE #14 GA. WIRE FOR LINE WIRING ON UNIT.
- USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.
FUSES AND SIZE ACCORDING TO 1.25 TIMES THE MAXIMUM TOTAL INPUT AMPS.
- WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH, USE DUAL ELEMENTS TIME DELAY
- DISCONNECT SWITCH IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS AN OPTION.
1, 4, 6, 7, 8,
- BLOWER MOTOR REMAINS ON AS DETERMINED BY FAN TIME DELAY.
- THE SENSING PROBE PROVES THE PRESENCE OF THE PILOT FLAME.
MAIN VALVE. THE MAIN GAS IGNITES AND UNIT FIRES AT FULL RATE.
- VENTER PRESSURE SWITCH CLOSES ENERGIZING THE PILOT GAS VALVE AND SPARK GAP TO PRODUCE A PILOT FLAME
ON EACH OPERATING CYCLE. THE SENSING PROBE PROVES THE PRESENCE OF THE PILOT FLAME AND ENERGIZING THE
SAFETY SWITCH PORTION OF THE CONTROL. THE SWITCH ACTION DE-ENERGIZES THE SPARK GAP AND ENERGIZES THE
- THERMOSTAT CALLS FOR HEAT ENERGIZING THE VENTER MOTOR.
- BLOWER MOTOR OPERATES FROM FAN TIME DELAY.
- SET THERMOSTAT AT LOWEST SETTING FOR SHUTDOWN.
- ENERGIZING THE GAS VALVE.
- DE-ENERGIZING THE IGNITOR.
- SET THERMOSTAT SWITCH AT DESIRED SETTING.
- TURN ON POWER, MAIN AND PILOT MANUAL GAS VALVES.
- SET THERMOSTAT SWITCH AT LOWEST SETTING.
OPERATING SEQUENCE
- IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION, THE SAFETY SWITCH CLOSES THE MAIN VALVE.
IF THE PILOT IS NOT ESTABLISHED WITHIN 120 SEC. THE UNIT LOCKS OUT FOR ONE HOUR, UNLESS IT IS RESET BY
INTERRUPTING POWER TO THE CONTROL CIRCUIT. (SEE LIGHTING INSTRUCTIONS)