Series 300 luminaires, Connecting to system – PRG DMX Reference Guide 5.4 User Manual
Page 84

76
DMX512 REFERENCE GUIDE
Series 300 Luminaires
Refer also to
Connecting to System
Series 300 luminaires require a Smart Repeater unit for power and control by DMX512 consoles.
Step
1. Position SixPack chassis delta/wye switches to correct setting.
"Configuring Equipment For Delta or Wye Operation"
Step
2. Connect Modular Rack to power source.
Three-phase power will need to be supplied to the system. The maximum recommended mod rack power
requirement is 200 amps, using 2/0 feeder with 4/0 Cam-Lok connectors and a 200A line disconnect. A
SixPack Chassis requires 30 amps, and uses Hubbell or Epic connectors on 8/5 multicore cable. Connector
choice is dependent upon location. This cable will need to be run from a house disconnect through a 30A
line disconnect to the racks.
WARNING:
The high voltages required to run this equipment are dangerous. Electrical "tie-ins" should be
handled by a qualified electrician.
Note: Some equipment in Europe will work using single-phase power. Check with an Account Manager regarding
your event.
Figure 3-28: Series 300 Modular Rack
To House
Disconnect
Tails
Series 200 AC Line
Disconnect
Modular Rack
Feeder Cable