Power and data distribution equipment, Ac line disconnect (200a) – PRG DMX Reference Guide 5.4 User Manual
Page 32

24
DMX512 REFERENCE GUIDE
POWER AND DATA DISTRIBUTION EQUIPMENT
AC Line Disconnect (200A)
CAUTION:
Although the maximum operating limit is 200A, we recommend that continuous operating
current does not exceed 150A.
The 200A AC line disconnect is a safety device containing a three-phase,
200A circuit breaker serving as a master on/off switch for the system. The
unit connects to house service through a set of five, 10-foot, 2/0 pig tails.
The line disconnect connects to the ACS rack through a set of five, 20-
foot and/or 80-foot, 2/0 pig tail cable assemblies. One line disconnect is
required for each 200A service.
Figure 2-1: AC Line Disconnect
OUTPUT
INPUT
Neutral (White)
X Phase (Black)
Y Phase (Red)
Z Phase (Blue)
Ground (Green)
Neutral (White)
X Phase (Black)
Y Phase (Red)
Z Phase (Blue)
Ground (Green)
Bare wire to Cam-Lok Pigtail cables
Cam-Lok to Cam-Lok
from House AC service
Pigtail cables to ACS or Mod Rack