Potter PFC-7501 User Manual
Page 23
19
10.4
Walk Test
The PFC-7500/PFC-7501 panels provide a walk test feature that allows a single technician to test the protection devices
connected to zones on the system. To conduct the Walk Test:
From the RA-7630 Keypad
1. From the keypad, enter the code 8144. If the system is monitored and the communication type is set to DD, the
system sends a System Test Begin report to the central station. The keypad then displays WALK TEST for four
seconds followed by TRIPS: X X X END. The " X X X " represents the number of trips that occur during the
Walk Test.
2. Once in the Walk Test, you can go around and trip each protection device. As each device is tripped, the panel
sounds the alarm bells for two seconds and then performs an automatic Sensor Reset. Continue tripping devices
until the entire system has been tested. The trip counter on the keypad display increments by one each time a device
is opened or shorted
3. To end the test, press the Select key under END. The panel sends a System Test End to the central station and performs a
final Sensor Reset. At the end of the test, the keypad displays any zones that failed to trip. Below are two examples:
Keypad display: SOUTH SMOK –FAIL
Keypad display: LOBBY HEAT –FAIL
From the RA-7692 LED Keypad
1. From the keypad, enter the code 8144. If monitored, the system sends a System Test Begin report to the central
station. The bottom row of zone LEDs (yellow) begin to pulse.
2. Once in the Walk Test, walk around and trip each protection device. As a device is tripped, the zone alarm LED on
the keypad turns on, the panel sounds the alarm bells for two seconds and the panel performs an automatic Sensor
Reset. The alarm LED stays on for the duration of the Walk Test.
Continue tripping devices until the entire system has been tested.
3. To end the test, press the RESET key and enter the user code or press COMMAND + 4 + 7. The panel sends a
System Test End to the central station.
10.5
Table of Common Keypad Messages
Message
Meaning
Possible Solutions
INVALID CODE The user code you entered is not recognized
by the system.
Check the user code and try again.
AC TROUBLE The system is not getting proper power.
Ensure the AC connections are good.
BATTERY
TROUBLE
Battery is either low or missing.
Ensure the battery connections are good and the battery is still
good.
SYSTEM
TROUBLE
or SERVICE
REqUIRED
There is a problem with one or more of the
components in the system.
Ensure there is not a short or open condition on the green data
wire to the keypad. You may also need to check that all of the
keypads and expansion modules on the bus are good.
SYSTEM BUSY The system is performing another task with a
higher priority.
Wait a few moments for the system to complete the task. If the
message displays for a long period of time, the processor could
be locked up.
TRANSMIT
TROUBLE
The panel attempted to communicate with
the central station three times and has not
succeeded.
Verify your communication type, account number, and phone
number. Ensure the telephone line is connected and working
properly.
ENTER CODE
(entering
Programming)
A lockout code is programmed into the panel. Enter the lockout code.
ONE MOMENT
The panel is dialing the Central Station to
indicate local programming session and off-
line status
Once the message is sent, programming resumes.