Output options – Potter PFC-7501 User Manual

Page 15

background image

11

6.1

OUTPUT OPTIONS

Output Options

This function allows you to program the panel Bell Output functions and certain Output options

for the Form C relays and annunciator outputs. Form C relay outputs are available on the panel

6-position terminal strip. Annunciator outputs (open collector) are available by using the 4-wire

output header on the PFC-7500/PFC-7501 board. Refer to the PFC-7500/PFC-7501 Installation

Manual (Stk# 8910227) for complete information. A description of each output option follows:

6.2

BELL CUTOFF:

15

Bell Cutoff Time

Enter the maximum time the Bell Output remains on. If the Bell Output is manually silenced

or the system is disarmed, the cutoff time resets. The Bell Cutoff Time can be from 1 to 15

minutes. Enter 0 (zero) to provide continuous bell output.

6.3

BELL ACTION . . . . .

Bell Action

This defines the type of Bell Output for zone alarms. Trouble conditions do not activate the

Bell Output. There are four bell actions you can program for Bell Output: To provide a steady

Bell Output, enter S. For a pulsed output, enter P. For Temporal Code 3, enter T. For California

School Code, enter C. For no Bell Output, enter N. Below is a list of the bell action for three of

the zone types:

6.3.1

FIRE

TYPE: P

Fire

Defines Bell Action for Fire and Fire Verify Type Zones

6.3.2

SUPRVSRY TYPE: N

Supervisory

Defines Bell Action for Supervisory Type Zones

6.3.3

AUXLRY I TYPE:

N

Auxiliary

Defines Bell Action for Auxiliary 1 Type Zones

6.4

OUTPUT ACTION . . .

Output Action

This option allows you to define the operation of the panel outputs.

6.4.1

CO OUTS: - - - -

Cutoff Outputs

Any or all of the available outputs can be programmed here to turn off after the time specified

in OUTPUT CUTOFF TIME. See the Output Cutoff Time section. To disable this option,

press any Select key to clear the display of output numbers and then press COMMAND.

6.4.2

CUTOFF TIME:

0

Output Cutoff Time

If a Cutoff Output is assigned, enter a Cutoff Time of up to 15 minutes for the output to remain

on. If the output is turned off manually, the Cut off Time resets. The Cutoff Time can be from 1

to 15 minutes.
Enter 0 (zero) to provide continuous output.
The Cutoff Timer is shared by all outputs. If a second output trips, the timer is not reset. Both

outputs turn off when the original time expires.

6.4.3

COM FAIL OUT:

0

Communication Failure Output

This output is turned on when a DD system fails to communicate with the receiver after ten

successive dial attempts.
Enter 0 (zero) to disable this output.

Output Options