This section allows you to select system wide parameters used in the operation of the PFC-
7500/PFC-7501 system.
5.2
CRS ZONE TM:
0
Cross Zone Fault Time
Enter the time allowed after a zone trips to indicate a zone fault condition. When a zone
programmed for cross zoning trips, the panel begins counting down the Cross Zone Fault Time
you enter here. If the same zone or another zone trips within this time, or prior to a Sensor
Reset, an alarm report is sent to the receiver for both zones.
If the Cross Zone Fault Time expires without the second zone trip, a zone fault report from the
first zone is sent to the receiver.
The Cross Zone Fault Time can be set from 4 to 250 seconds in one second increments. Enter 0
(zero) to disable the Cross Zone Fault Time feature.
5.3
RETARD DLY:
0
Zone Retard Delay
Enter the time allowed for zones to be shorted before the panel acknowledges the short as an
alarm. This option is primarily used on waterflow zones where fluctuations in the flowswitch
may short the zone in the absence of an actual alarm condition.
The Retard Delay can be set from 0 to 250 seconds in one-second increments.
5.4
PWR FAIL hRS:
1
Power Fail Delay
This option tracks the duration of an AC power failure. When the AC power is off for the length
of the programmed delay time, an AC power failure report is sent to the receiver.
The delay time can be set from 0 to 15 hours. Default is 1.
5.5
RST SBYP NO YES
Reset Swinger Bypass
When YES is selected, a swinger bypassed zone is automatically reset if it remains in a normal
condition for one hour after being bypassed. A report of the reset is automatically sent to the receiver.