Potter PFC-7501 User Manual
Page 11
7
3.10
BACKUP
NO YES
Backup Reporting
YES enables Receiver 1 to be a backup to Receiver 2 in the event the panel cannot contact
Receiver 2.
3.11
-
-
FIRST PhONE NO:
First Telephone Number
This is the first number the panel dials when sending reports to this receiver. A phone number
can consist of two lines of 16 characters to equal 32 characters. You can program a three second
pause in the dial ing se quence by en tering the let ter P. You can program a dial tone detect by
entering the letter D. These characters are counted as part of the 32 allowable characters.
3.12
-
-
SECOND PhONE NO:
Second Telephone Number
The panel dials the second number when two successive tries using the first number fail. If the
panel cannot reach the receiver after two attempts using the second number, it returns to the
first number and makes two additional attempts. A total of ten dialing attempts are made using
the first and second phone num bers. If a second phone number is not entered, the first phone
number is used for all dialing attempts.
Each number can be up to 32 characters in length in cluding any P or D char acters entered for
pause and dial tone detect.
3.13
RECEIVER 2 PROG
Receiver 2 Programming
Receiver 2 defaults are set to NO. If you select YES for any Receiver 2 options, you must have
at least one phone number programmed in Receiver 2 programming.
3.14
PAGER?
NO YES
Pager Type
This option allows the panel to send Alarm and Trouble reports to a customer's numeric pager.
The panel uses DTMF tones for numeric pagers. Selecting NO allows you to use the Receiver 2
Programming to send panel reports to a second receiver.
Note: The XR5 communicates in a half-duplex mode with a Glenayre alphanumeric pager
terminal. The terminal modem must accept the following parameters:
•
300 bps Bell 103 protocol
•
Carrier detect response time = 300ms
•
Delay between lost carrier and hang-up = 12.0 seconds
3.15
ALARM
NO YES
Alarm Reports
See Receiver 1 Alarm Reports section for programming.
3.16
SPV/TRBL NO YES
Supervisory/Trouble Reports
See Receiver 1 Supervisory/Trouble Reports section for programming.
3.17
TEST RPT NO YES
Test Report
Enter YES to enable the Recall Test report to be sent to this receiver. When 2nd line is YES,
the Recall Test message alternates between the two phone lines. The message is sent on the
phone line designated for that day even when the supervision circuit indicates the phone line is
bad. This allows both phone lines to be tested as required by NFPA.
3.18
BACKUP
NO YES
Backup Reporting
YES enables Receiver 2 to be a backup to Receiver 1 in the event the panel cannot contact
Receiver 1.