Potter PFC-7501 User Manual
Page 16
12
6.4.4
FIRE ALR OUT:
0
Fire Alarm Output
This output is turned on any time a fire type zone is placed in alarm. The output is turned off
using the Sensor Reset option when no additional fire type zones are in alarm. Enter 0 (zero) to
disable this output.
6.4.5
FIRE TRB OUT:
0
Fire Trouble Output
This output is turned on any time a fire type zone is placed in trouble, when a supervisory type
zone is placed in alarm or trouble, or when AC power, battery power, or either phone line is
in trouble. The output is turned off when all trouble conditions are restored to normal. Enter 0
(zero) to disable this output.