7.5

NEXT ZN? NO YES

Next Zone?

When YES is selected, the programming for the zone terminates and the display returns to

ZONE NO: - allowing you to enter a new zone number. To make changes to the Alarm Action

for a zone, answer the NEXT ZONE? prompt with NO. The Alarm Action is then defined in

the following sections.

7.6

ALARM ACTION . . . .

Alarm Action

The Alarm Action section allows you to change or confirm the default alarm characteristics of a

zone type.
The Fire Verify zone type functions the same as Fire zone with the following exceptions: When a

Fire Verify zone is placed into shorted condition, the panel performs a Sensor Reset and does not

send a report. If any Fire Verify or Fire zone initiates an alarm within 120 seconds after the reset,

an alarm is indicated. If an alarm is initiated after 120 seconds, the cycle repeats. If no other Fire

Verify or Fire zone is alarmed within 120 seconds, a zone fault report is sent to the receiver.

7.7

Zone Type Specifications

The PFC-7500/PFC-7501 panels contain four default zone types for use in configuring the system. These zone types

provide the most commonly selected functions for their applications.

Zone Information

Type Open

Short

Swinger

Bypass

Retard

Delay

Cross

Zone

Use this section of the

programming sheet to record the

program options you selected for

the XR5 panel zone.

FI

SV
A1
FV

Message

Output

Action

Message

Output

Action

A

T

L

0

to

4

S

P

M

F

A

T

L

0

to

4

S

P

M

F

N

or

Y

N

or

Y

N

or

Y

Fire

FI

T

0

A

0

N

N

N

Supervisory

SV

T

0

A

0

N

N

N

Auxiliary 1

A1

T

0

A

0

N

N

N

Fire Verify

FV

T

0

A

0

N

N

No.

Zone Name

1

2

3

4

5

31

32

33

34

Programmable Zone Options Descriptions

Below is a description of the various zone options shown on the table above.
Zone Information - The complete spellings of the abbreviations used for the zone types.
Type - The abbreviations that display on the keypad for the zone types.
Message - A = alarm report, T = trouble report, L = local with no report,

(dash) = no report.

Output - This only refers to the four PFC-7500/PFC-7501 relay outputs.
Action - This selects the type of relay output: S = steady, P = pulse, M = momentary, and F = follow
Swinger Bypass - Allows the zone to be automatically bypassed after three trips.
Retard Delay - Provides a time delay before an alarm initiates from a short on this zone.
Cross Zone - Provides cross zoning for this zone.