beautypg.com

Thermostat wiring, Indoor & outdoor split geothermal comfort systems – Carrier GT-S User Manual

Page 41

background image

Indoor & Outdoor Split

Geothermal Comfort Systems

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

39

Thermostat Wiring

Thermostat Installation
The thermostat should be located on an interior wall in
a larger room, away from supply duct drafts. DO NOT
locate the thermostat in areas subject to sunlight, drafts
or on external walls. The wire access hole behind the
thermostat may in certain cases need to be sealed to
prevent erroneous temperature measurement. Position
the thermostat back plate against the wall so that it
appears level and so the thermostat wires protrude
through the middle of the back plate. Mark the position
of the back plate mounting holes and drill holes with a
3/16” (5mm) bit. Install supplied anchors and secure
plate to the wall. Thermostat wire must be 18 AWG wire.
Wire the appropriate thermostat as shown in Figures
28a through 28c to the low voltage terminal strip on
the CXM control board. Practically any heat pump
thermostat will work with these units, provided it has the
correct number of heating and cooling stages.

Typical Thermostat Wiring, Single-Stage
Units (2 Heat / 1 Cool)

Typical Thermostat Wiring, Two-Stage Units
(3 Heat / 2 Cool)

Y

O

R

C

Y1/W2

O/W2

G

R

W1

W2

W/W1

FV4

Air Handler

TSTAT CCPRH01

or BBPRH01

CXM Board

(Compressor

Section)

O

G

R

C

Y/Y2

Y1

Y/Y2

From Compressor

Solenoid Valve

Hum

Humidifier

Sol. Vlv. 24VAC

S1

S2

Outdoor

Sensor

DHum

DH

C

Remove Jumper

for Dehum Mode

Notes:
1. Thermostat DIP switches must be configured for two-speed heat pump.
2. Compressor 2nd stage connection is not part of the terminal strip on
the CXM board. A wire nut connection is required between the
compressor solenoid valve and Y/Y2 connection at the fan coil.

Y

O

R

C

Y1/W2

O/W2

G

R

W1

W2

W/W1

FV4

Air Handler

TSTAT CCPRH01

or BBPRH01

CXM Board

(Compressor

Section)

O

G

R

C

Y/Y2

Y1

Y/Y2

From Compressor

Solenoid Valve

Hum

Humidifier

Sol. Vlv. 24VAC

S1

S2

Outdoor

Sensor

DHum

DH

C

Remove Jumper

for Dehum Mode

Notes:
1. Thermostat DIP switches must be configured for two-speed heat pump.
2. Compressor 2nd stage connection is not part of the terminal strip on
the CXM board. A wire nut connection is required between the
compressor solenoid valve and Y/Y2 connection at the fan coil.

Typical Thermostat Wiring,
Infi nity / Evolution Controls

Y

O

C

R

B

Network

Interface Module

FE4 or Other

Communicating

Indoor Unit

CXM Board

(Compressor

Section)

O

R

Y1

Y2

From Compressor

Solenoid Valve

(Notes 1,2)

A

D

Notes:
1. Compressor 2nd stage connection is not part of the terminal strip on
the CXM board. A wire nut connection is required between the
compressor solenoid valve and N.I.M.
2. Y2 connection on N.I.M. is not used for single stage units.

C

C

B

User

Interface

D

A

C

B

D

A

C

This manual is related to the following products: