Carrier – Carrier GT-S User Manual
Page 30

Carrier
Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05
28
50YCS024 / 38WQS024 With GAH024
Performance capacities shown in thousands of Btuh.
WPD
HEATING - EAT 70
°F
COOLING - EAT 80/67
°F
EWT
°F
GPM
PSI
FT
CFM
HC
KW
HE
LAT
COP
HWC
TC
SC
KW
HR
EER
HWC
3.0
0.4
1.0
650
800
Operation not recommended
20
4.5
1.0
2.2
650
Operation not recommended
800
6.0
1.7
3.9
650
16.0
1.62
10.5
92.8
2.89
2.1
800
16.2
1.59
10.8
88.7
2.99
1.8
3.0
0.4
0.9
650
18.9
1.69
13.2
97.0
3.29
2.4
29.4
19.3
0.92
32.6
32.1
0.9
800
19.2
1.62
13.7
92.3
3.48
2.0
31.0
21.2
0.94
34.2
33.0
0.8
30
4.5
0.9
2.1
650
19.1
1.69
13.4
97.2
3.32
2.5
30.0
19.6
0.89
33.0
33.8
1.0
800
19.4
1.64
13.8
92.4
3.47
2.1
31.0
21.2
0.91
34.1
34.3
0.8
6.0
1.6
3.8
650
19.3
1.69
13.5
97.5
3.35
2.6
30.6
19.9
0.86
33.5
35.6
1.0
800
19.5
1.65
13.9
92.6
3.47
2.2
31.1
21.2
0.87
34.1
35.6
0.8
3.0
0.4
0.9
650
21.5
1.75
15.6
100.7
3.60
2.8
28.7
18.7
1.10
32.4
26.2
1.6
800
21.9
1.69
16.1
95.3
3.80
2.4
30.2
20.6
1.12
34.0
26.9
1.4
40
4.5
0.9
2.1
650
21.9
1.77
15.9
101.2
3.63
2.9
29.2
19.0
1.06
32.8
27.6
1.5
800
22.2
1.70
16.3
95.6
3.81
2.5
30.2
20.6
1.08
33.9
28.0
1.4
6.0
1.6
3.7
650
22.3
1.78
16.2
101.8
3.67
3.0
29.7
19.3
1.02
33.1
29.1
1.3
800
22.5
1.72
16.6
96.0
3.82
2.6
30.2
20.6
1.04
33.8
29.2
1.3
3.0
0.4
0.9
650
24.1
1.82
17.9
104.4
3.88
3.2
27.9
18.2
1.28
32.3
21.9
2.2
800
24.5
1.75
18.5
98.3
4.10
2.8
29.4
20.0
1.31
33.8
22.5
2.1
50
4.5
0.9
2.0
650
24.7
1.85
18.4
105.2
3.92
3.3
28.4
18.4
1.23
32.5
23.1
2.0
800
24.9
1.77
18.9
98.9
4.13
2.9
29.3
20.0
1.25
33.6
23.4
2.0
6.0
1.6
3.6
650
25.3
1.87
18.9
106.1
3.96
3.4
28.8
18.7
1.18
32.8
24.4
1.7
800
25.4
1.79
19.3
99.4
4.16
3.0
29.3
20.0
1.20
33.4
24.4
1.8
3.0
0.4
0.9
650
26.6
1.90
20.1
107.9
4.09
3.6
27.0
18.0
1.42
31.9
19.0
2.7
800
27.1
1.82
20.9
101.4
4.38
3.2
28.4
19.6
1.46
33.4
19.5
2.7
60
4.5
0.8
1.9
650
27.5
1.93
20.9
109.1
4.16
3.8
27.2
18.1
1.36
31.9
20.0
2.4
800
27.9
1.84
21.6
102.3
4.43
3.3
28.2
19.6
1.39
32.9
20.3
2.5
6.0
1.5
3.5
650
28.4
1.96
21.7
110.4
4.23
3.9
27.4
18.3
1.30
31.9
21.2
2.2
800
28.7
1.87
22.3
103.2
4.49
3.4
28.0
19.7
1.32
32.5
21.2
2.3
3.0
0.4
0.8
650
29.0
1.98
22.3
111.3
4.29
4.1
26.1
17.8
1.57
31.5
16.7
3.2
800
29.7
1.88
23.3
104.4
4.63
3.5
27.5
19.3
1.61
33.0
17.1
3.2
70
4.5
0.8
1.9
650
30.2
2.02
23.3
113.0
4.38
4.2
26.1
17.9
1.49
31.2
17.5
2.9
800
30.8
1.92
24.3
105.7
4.72
3.7
27.0
19.3
1.53
32.3
17.7
3.0
6.0
1.5
3.4
650
31.4
2.06
24.4
114.7
4.47
4.3
26.1
18.0
1.41
30.9
18.4
2.7
800
32.0
1.95
25.3
107.0
4.80
3.8
26.6
19.4
1.44
31.5
18.4
2.8
3.0
0.3
0.8
650
31.6
2.05
24.6
115.0
4.51
4.5
25.4
17.1
1.77
31.5
14.4
3.6
800
32.4
1.95
25.7
107.4
4.87
3.9
26.8
18.5
1.81
32.9
14.8
3.7
80
4.5
0.8
1.8
650
32.9
2.09
25.8
116.9
4.60
4.7
25.4
17.2
1.68
31.1
15.1
3.4
800
33.6
1.99
26.8
108.9
4.96
4.0
26.3
18.6
1.72
32.2
15.3
3.5
6.0
1.4
3.2
650
34.3
2.14
27.0
118.8
4.69
4.8
25.4
17.2
1.59
30.8
16.0
3.1
800
34.9
2.03
28.0
110.4
5.04
4.2
25.9
18.6
1.62
31.4
15.9
3.2
3.0
0.3
0.8
650
34.2
2.12
26.9
118.6
4.72
5.0
24.7
16.4
1.96
31.4
12.6
4.1
800
35.0
2.01
28.1
110.5
5.10
4.2
26.0
17.7
2.01
32.9
12.9
4.3
90
4.5
0.8
1.7
650
35.6
2.17
28.2
120.8
4.81
5.2
24.7
16.4
1.86
31.1
13.3
3.9
800
36.4
2.06
29.4
112.1
5.18
4.4
25.6
17.8
1.91
32.1
13.4
4.0
6.0
1.4
3.1
650
37.1
2.22
29.5
122.9
4.89
5.4
24.7
16.5
1.77
30.7
14.0
3.6
800
37.8
2.11
30.6
113.8
5.25
4.6
25.2
17.9
1.80
31.3
14.0
3.7
3.0
0.3
0.7
650
23.4
15.9
2.20
30.9
10.6
4.6
800
24.6
17.2
2.26
32.3
10.9
4.8
100
4.5
0.7
1.7
650
23.3
16.0
2.09
30.5
11.2
4.4
800
24.2
17.3
2.14
31.5
11.3
4.5
6.0
1.3
3.0
650
23.3
16.0
1.98
30.1
11.8
4.1
800
Operation not recommended
23.8
17.3
2.02
30.7
11.8
4.2
3.0
0.3
0.7
650
22.0
15.4
2.44
30.3
9.0
5.1
800
23.2
16.7
2.50
31.7
9.3
5.3
110
4.5
0.7
1.6
650
22.0
15.5
2.32
29.9
9.5
4.8
800
22.8
16.7
2.37
30.9
9.6
5.0
6.0
1.3
2.9
650
21.9
15.5
2.20
29.4
10.0
4.6
800
22.4
16.8
2.24
30.0
10.0
4.7
Rev: 12/12/03 B
Operation below 40
°F EWT is based on 15% antifreeze solution.
See performance correction tables for operating conditions other than those listed above.
Table does not reflect fan or pump power ISO corrections.
Interpolation is permissable, extrapolation is not.
All entering air conditions are 80
°F DB and 67°F WB in cooling and 70°F DB in heating.
All performance data is based upon the lower voltage of dual voltage rated units.