beautypg.com

Indoor & outdoor split geothermal comfort systems – Carrier GT-S User Manual

Page 35

background image

Indoor & Outdoor Split

Geothermal Comfort Systems

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

33

50YCS060 / 38WQS060 With GAH060

Performance capacities shown in thousands of Btuh.

WPD

HEATING - EAT 70

°F

COOLING - EAT 80/67

°F

EWT

°F

GPM

PSI

FT

CFM

HC

KW

HE

LAT

COP

HWC

TC

SC

KW

HR

EER

HWC

7.5

1.6

3.7

1650

2000

Operation not recommended

20

11.3

3.2

7.4

1650

Operation not recommended

2000

15.0

5.1

11.8

1650

41.1

4.04

27.3

93.0

2.98

5.3

2000

41.5

3.99

27.9

89.2

3.05

4.5

7.5

1.6

3.6

1650

43.1

4.09

29.2

94.2

3.09

6.0

67.5

44.2

2.64

76.5

25.5

2.2

2000

43.8

4.05

30.0

90.3

3.17

5.0

69.1

47.2

2.73

78.5

25.3

1.8

30

11.3

3.1

7.1

1650

45.5

4.13

31.4

95.5

3.23

6.2

67.6

43.9

2.58

76.4

26.2

2.3

2000

46.1

4.09

32.2

91.4

3.30

5.3

68.8

46.7

2.68

77.9

25.7

1.9

15.0

4.9

11.4

1650

47.9

4.18

33.6

96.9

3.36

6.4

67.6

43.6

2.52

76.2

26.9

2.3

2000

48.5

4.13

34.4

92.4

3.44

5.5

68.4

46.1

2.63

77.4

26.0

2.0

7.5

1.5

3.5

1650

50.4

4.29

35.8

98.3

3.45

7.0

65.3

43.5

3.05

75.7

21.4

3.8

2000

51.3

4.25

36.8

93.7

3.54

6.0

66.8

46.5

3.15

77.6

21.2

3.5

40

11.3

3.0

6.9

1650

53.0

4.35

38.2

99.8

3.57

7.3

65.4

43.3

2.96

75.5

22.1

3.5

2000

53.3

4.28

38.7

94.7

3.65

6.2

66.5

46.0

3.07

77.0

21.7

3.4

15.0

4.8

11.1

1650

55.7

4.42

40.6

101.3

3.69

7.5

65.5

43.0

2.86

75.2

22.9

3.2

2000

55.3

4.32

40.6

95.6

3.75

6.5

66.3

45.5

2.99

76.5

22.1

3.2

7.5

1.5

3.4

1650

57.7

4.48

42.4

102.4

3.77

8.0

63.1

42.9

3.46

74.9

18.2

5.4

2000

58.7

4.44

43.5

97.2

3.87

7.0

64.6

45.8

3.58

76.8

18.1

5.2

50

11.3

2.9

6.7

1650

60.6

4.57

45.0

104.0

3.88

8.3

63.2

42.6

3.34

74.6

18.9

4.8

2000

60.4

4.48

45.2

98.0

3.96

7.2

64.3

45.3

3.47

76.1

18.6

4.8

15.0

4.6

10.7

1650

63.5

4.66

47.6

105.6

3.99

8.6

63.3

42.4

3.21

74.2

19.7

4.1

2000

62.2

4.51

46.8

98.8

4.04

7.5

64.1

44.8

3.36

75.5

19.1

4.4

7.5

1.4

3.3

1650

64.9

4.68

48.9

106.4

4.06

9.1

61.6

41.9

3.78

74.6

16.3

6.6

2000

66.1

4.64

50.3

100.6

4.17

7.9

63.1

45.4

3.90

76.4

16.2

6.5

60

11.3

2.8

6.5

1650

68.1

4.79

51.7

108.2

4.16

9.4

61.9

41.7

3.61

74.2

17.1

6.0

2000

68.5

4.67

52.6

101.7

4.30

8.2

63.2

45.0

3.74

75.9

16.9

6.1

15.0

4.5

10.4

1650

71.3

4.90

54.5

110.0

4.26

9.7

62.1

41.4

3.45

73.9

18.0

5.4

2000

71.0

4.71

54.9

102.9

4.42

8.5

63.2

44.6

3.58

75.4

17.7

5.6

7.5

1.4

3.2

1650

72.2

4.88

55.5

110.5

4.33

10.1

60.2

41.0

4.11

74.2

14.7

7.8

2000

73.5

4.83

57.0

104.0

4.45

8.9

61.7

45.0

4.23

76.1

14.6

7.9

70

11.3

2.7

6.3

1650

75.6

5.01

58.5

112.4

4.42

10.4

60.6

40.7

3.89

73.9

15.6

7.2

2000

76.6

4.87

60.0

105.5

4.61

9.2

62.0

44.7

4.02

75.7

15.4

7.3

15.0

4.3

10.0

1650

79.0

5.15

61.5

114.4

4.50

10.8

61.0

40.4

3.68

73.5

16.6

6.6

2000

79.7

4.90

63.0

106.9

4.77

9.5

62.4

44.3

3.80

75.4

16.4

6.8

7.5

1.3

3.1

1650

79.4

5.08

62.1

114.6

4.58

11.3

57.6

40.2

4.56

73.2

12.6

9.0

2000

80.9

5.03

63.7

107.5

4.71

9.7

59.0

44.2

4.70

75.0

12.5

9.2

80

11.3

2.6

6.1

1650

82.7

5.20

64.9

116.4

4.66

11.7

58.0

40.0

4.32

72.7

13.4

8.4

2000

83.8

5.05

66.6

108.8

4.86

10.1

59.3

43.8

4.46

74.5

13.3

8.6

15.0

4.2

9.7

1650

86.0

5.33

67.8

118.2

4.73

12.1

58.3

39.7

4.09

72.3

14.3

7.8

2000

86.7

5.07

69.4

110.1

5.01

10.5

59.7

43.5

4.22

74.1

14.1

8.0

7.5

1.3

3.0

1650

86.7

5.28

68.7

118.7

4.81

12.5

55.0

39.5

5.02

72.1

11.0

10.2

2000

88.3

5.23

70.5

110.9

4.95

10.5

56.3

43.4

5.17

73.9

10.9

10.6

90

11.3

2.5

5.9

1650

89.8

5.39

71.4

120.4

4.88

13.0

55.3

39.2

4.76

71.5

11.6

9.6

2000

91.0

5.24

73.1

112.1

5.09

11.0

56.6

43.0

4.90

73.3

11.5

9.9

15.0

4.1

9.4

1650

92.9

5.51

74.1

122.1

4.94

13.5

55.6

39.0

4.49

71.0

12.4

9.0

2000

93.7

5.25

75.8

113.4

5.23

11.5

56.9

42.7

4.64

72.8

12.3

9.2

7.5

1.2

2.9

1650

53.3

39.1

5.56

72.3

9.6

11.5

2000

54.6

42.9

5.72

74.1

9.5

11.9

100

11.3

2.4

5.6

1650

53.7

38.8

5.27

71.6

10.2

10.8

2000

54.9

42.6

5.43

73.5

10.1

11.2

15.0

3.9

9.0

1650

54.0

38.5

4.98

71.0

10.8

10.2

2000

Operation not recommended

55.3

42.2

5.14

72.8

10.7

10.4

7.5

1.2

2.8

1650

51.7

38.6

6.10

72.5

8.5

12.8

2000

52.9

42.5

6.28

74.4

8.4

13.3

110

11.3

2.4

5.4

1650

52.0

38.4

5.78

71.8

9.0

12.1

2000

53.3

42.1

5.96

73.6

8.9

12.5

15.0

3.8

8.7

1650

52.4

38.1

5.46

71.0

9.6

11.4

2000

53.6

41.8

5.64

72.8

9.5

11.6

Rev: 12/12/03 B

Interpolation is permissable, extrapolation is not.

All entering air conditions are 80

°F DB and 67°F WB in cooling and 70°F DB in heating.

All performance data is based upon the lower voltage of dual voltage rated units.

Operation below 40

°F EWT is based on 15% antifreeze solution.

See performance correction tables for operating conditions other than those listed above.

Table does not reflect fan or pump power ISO corrections.

This manual is related to the following products: